H
Y branch method
Combination of Y
branch/header Method
Header Method
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Indoor Units
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Header
Ⓕ
: Sealed piping
Ⓐ
: Outdoor Unit
Ⓑ
: Header branch
Ⓒ
: Indoor Units
Ⓓ
: Sealed piping
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Indoor Units
Ⓓ
: Downward Indoor Unit
Ⓔ
: Connection branch
pipe between
Outdoor units:
ARCNN31
Ⓕ
: Connection branch
pipe between
Outdoor units:
ARCNN21
l
40 m (90 m : Conditional application)
h 30 m
H
9
0
m
L165 m
L 165 m
40 m(90 m : Conditional application)
H
9
0
m
3
0
m
L 165 m
40 m
H
9
0
m
30 m
1 Outdoor Units
Y branch method
Combination of Y branch/
header Method
Header Method
Ⓐ
: Outdoor Unit
Ⓑ
: Header branch
Ⓒ
: Indoor Units
Ⓓ
: Sealing
Ⓔ
: Connection branch pipe
between Outdoor
units : ARCNN41
Ⓕ
: Connection branch pipe
between Outdoor
units : ARCNN31
Ⓖ
: Connection branch pipe
between Outdoor
units : ARCNN21
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch(Y branch)
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Connection branch pipe
between Outdoor
units : ARCNN41
Ⓕ
: Connection branch pipe
between Outdoor
units : ARCNN31
Ⓖ
: Connection branch pipe
between Outdoor
units : ARCNN21
Ⓗ
: Header
Ⓘ
: Sealing
10 m or
less
L165 m
l
40 m (90 m : Conditional application)
H
9
0
m
Slave2
Slave3
Slave1
Master
G
ODU Capacity
Master ≥ Slave1 ≥ Slave 2 ≥ Slave 3
h 30 m
h1
10 m or
less
H
9
0
m
G
G
FF
EE
G
F
E
L 165 m
l
40 m(90 m : Conditional application)
ODU Capacity
Master ≥ Slave1 ≥ Slave2 ≥ Slave3
3
0
m
Master
Slave3
Slave1
Slave2
h1
10 m or
less
H
9
0
m
L 165 m
40 m
Master
Slave3
Slave1
Slave2
ODU Capacity
Master ≥ Slave1 ≥ Slave2 ≥ Slave3
30 m
G
G
G
h1
F
F
E
E
F
E
h
See Table 2
A : Refrigerant pipe diameter from outdoor unit to first branch
E : Refrigerant pipe diameter for outdoor unit capacity
(Slave 1+ Slave 2+ Slave 3)
F : Refrigerant pipe diameter for outdoor unit capacity
(Slave 2+ Slave 3)
G : Refrigerant pipe diameter for outdoor unit capacity(Slave 3)
h
* : See Table 4
L1
L2
L3
h1
E
G
F
Slave3
Slave2
Slave1
Master
l
40 m
h 30 m
Indoor
Unit
1st branch
Refrigerant pipe diameter from outdoor unit to first branch
Level Difference
(Outdoor unit
↔
Outdoor unit)
5m
Max length from first branch to
each outdoor unit (L1, L2, L3)
Less than 10 m
(equivalent length of piping 13 m)
Y branch
Method
Combination of Y
branch/header
Method
Header
Method
Max pipe
length
Outdoor Unit
↔
Indoor Unit
Longest
pipe
length(L)
A+B+C+D+e
≤
165 m A+B+b
≤
165 m
A+C+e
≤
165 m A+f
≤
165 m
Equivalent
pipe length
190 m
190 m
190 m
Total pipe
length
1,000 m
1,000 m
1,000 m
Max
difference
in height
Outdoor Unit
↔
Indoor Unit
Difference in
height(H)
90 m
90 m
90 m
Indoor Unit
↔
Indoor Unit
Difference in
height(h)
30 m
30 m
30 m
Longest pipe
length after
1st branch
Pipe
length(l)
40 m
(90 m: Conditional
application)*
40 m
(90 m: Conditional ap-
plication)*
40 m
(Table 1) Limit Pipe length