19
ENGLISH
h
h
0.2m
Toward indoor unit
Toward indoor unit
Oil Trap
(Example 3)
The amount of Refrigerant
The calculation of the additional charge should take into account the
length of pipe and CF(correction Factor) value of indoor unit.
Total liquid pipe : Ø25.4 mm
Additional charge(kg)
Total liquid pipe : Ø22.2 mm
Total liquid pipe : Ø19.05 mm
Total liquid pipe : Ø15.88 mm
Total liquid pipe : Ø12.7 mm
Total liquid pipe : Ø9.52 mm
Total liquid pipe : Ø6.35 mm
Number of installed HR units
CF value of indoor unit
=
+
+
+
+
+
+
+
x 0.480(kg/m)
x 0.354(kg/m)
x 0.266(kg/m)
x 0.173(kg/m)
x 0.118(kg/m)
x 0.061(kg/m)
x 0.022(kg/m)
x 0.5(kg/m)
Amount refrigerant of Indoor units
Example) 4Way Ceiling Cassette 14.5kW -1ea, Ceiling concealed
Duct 7.3kW-2ea,
Wall Mounted 2.3kW-4ea
CF = 0.64 × 1 + 0.26 × 2 + 0.24 × 4 = 2.12 kg
CAUTION
Use only 2-series of indoor unit. Ex) ARNU***2
Do not connect Hydro kit with Multi V IV Models.
!
Toward indoor unit
Toward indoor unit
Pipe inclination (2° or more)
Toward indoor unit
Toward indoor unit
Toward indoor unit
Toward indoor unit
(Example 1)
(Example 2)
(Example 3)
- Apply Oil Trap as shown below when the length of the pipe between
the outdoor units is more than 2m. Otherwise, the unit may not oper-
ate properly.
(Example 1)
Toward indoor unit
Toward indoor unit
2m
2m
2m
0.2m
Oil Trap
(Example 2)
- When connecting the pipes between the outdoor units, the accumu-
lation of oil in the slave outdoor unit should be avoided. Otherwise,
the unit may not operate properly.
(Example 1)
Toward indoor unit
Toward indoor unit
h
Toward indoor unit
(Example 2)
Attach the additional refrigerant table of IDU.