16
ENGLISH
Refrigerant pipe diameter from outdoor unit to first
branch. (A)
Y branch, Header and HR unit connection pattern
Upward
outdoor
unit total
capacity
Pipe diameter
Pipe diameter when pipe length is
90m over to 1st branch
HP
Liquid
mm(inch)
Low pres-
sure gas
pipe
mm(inch)
High pres-
sure gas
pipe
mm(inch)
Liquid
mm(inch)
Low pres-
sure gas
pipe
mm(inch)
High pres-
sure gas
pipe
mm(inch)
8
9.52(3/8)
19.05(3/4) 15.88(5/8)
12.7(1/2)
22.2(7/8) 19.05(3/4)
10
22.2(7/8)
19.05(3/4)
25.4(1)
22.2(7/8)
12
12.7(1/2)
28.58(1-1/8)
15.88(5/8)
31.8(1-1/4)
14
22.2(7/8) 25.4(1)
16
18
15.88(5/8) 19.05(3/4)
20
22
34.9(1-3/8)
28.58(1-1/8)
38.1(1-1/2)
31.8(1-1/4)
24
26
19.05(3/4) 22.2(7/8)
28
30
32
34
36
41.3(1-5/8) 44.5(1-3/4)
38
40
42
34.9(1-3/8) 38.1(1-1/2)
44
46
48
50
52
54
56
58
60
62
22.2(7/8)
44.5(1-3/4) 41.3(1-5/8)
25.4(1) 53.98(2-1/8)
44.5(1-3/4)
64
66
53.98(2-1/8) 44.5(1-3/4)
53.98(2-1/8)
68
70
72
74
76
78
80
* If available on site, it use this size. Otherwise it can't be increased.
Pattern 1
HR1
48k
48k
1
2
HR2
48k
48k
3
4
B
• Impossible installation : Head branch pipe HR unit
Refrigerant pipe diameter from branch to branch (B,C,D)
- * : Assume equivalent pipe length of Y branch to be 0.5m, that of
header to be 1m, calculation purpose
- It is recommended that indoor unit is installed at lower position than
the header.
- ** : To apply conditional application.
3) Length of pipe from each indoor unit to the HR Unit
(a,b,c,d,e,f,g,i,j,k,l,m,n)
≤
40 m
4) [Length of pipe from outdoor unit to the farthest indoor unit D12
(A+B+C+D+e)]
- [Length of pipe outdoor unit to the closest indoor unit D1(C1+a)]
≤
40
m
WARNING
* : Serial connection of HR units : Capacity sum of indoor units ·
192.4 kBtu/hr
• Refer to the HR unit PCB part for the valve group control setting.
• It is recommended that difference in pipe lengths between an HR
unit and indoor units, for example
difference in length of a, b, c, and d, be minimized. The larger dif-
ference in pipe lengths, the more different performance between
indoor units.
• Piping length from outdoor branch to outdoor unit
≤
10m, equiva-
lent length : max 13m (for 22HP or more)
* If the large capacity indoor units (Over 5 HP; using over
Ø15.88/Ø9.52) are installed, it should be used the Valve Group
setting
!
Refrigerant pipe diameter from branch to branch (B,C)
Downward indoor
unit total capacity
[kW(Btu/h)]
Liquid pipe
[mm(inch)]
Gas pipe [mm(inch)]
Low pressure
High pressure
≤
5.6(19,100)
Ø6.35(1/4)
Ø12.7(1/2)
Ø9.52(3/8)
< 16.0 (54,600)
Ø9.52(3/8)
Ø15.88(5/8)
Ø12.7(1/2)
< 22.4 (76,400)
Ø9.52(3/8)
Ø19.05(3/4)
Ø15.88(5/8)
< 33.6(114,700)
Ø9.52(3/8)
Ø22.2(7/8)
Ø19.05(3/4)
< 50.4(229,000)
Ø12.7(1/2)
Ø28.58(1 1/8)
Ø22.2(7/8)
< 61.6(210,600)
Ø15.88(5/8)
Ø28.58(1 1/8)
Ø22.2(7/8)
< 72.8(210,600)
Ø15.88(5/8)
Ø34.9(1 3/8)
Ø28.58(1 1/8)
< 100.8(344,000)
Ø19.05(3/4)
Ø34.9(1 3/8)
Ø28.58(1 1/8)
< 173.6(592,500)
Ø19.05(3/4)
Ø41.3(1 5/8)
Ø34.9(1 3/8)
< 184.8(630,700)
Ø22.2(7/8)
Ø44.5(1 3/4)
Ø41.3(1 5/8)
≤
224.0(764,400)
Ø22.2(7/8)
Ø53.98(2 1/8)
Ø44.5(1 3/4)
Total pipe length = A + B + C1 + C2 + C3 + a + b + c + d
+ e + f + g + i + j + k + l + m + n ≤ 1,000m
L
Longest pipe length
* Equivalent pipe length
A+B+C3+D+k
≤
150m(200m**) A+B+C3+D+k
≤
175m(225m**)
l
Longest pipe length after 1st branch
B+C3+D+k
≤
40m(90m**)
H
Difference in height(Outdoor Unit
÷
Indoor Unit)
H
≤
110m
h
Difference in height (Indoor Unit
÷
Indoor Unit)
h
≤
40m
h1
Difference in height (Outdoor Unit
÷
Outdoor Unit)
h1
≤
5m
"a", "b"
Difference in height(HR unit
÷
HR unit)
a
≤
15m , b
≤
5m ,
WARNING
When the equivalent length between a outdoor and the farthest in-
door unit is 90m or more, main pipe(A) must be increased one
grade.
!