35
ENGLISH
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn6” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“op1” ~ “op3” Push the ‘
●
’ button
Mode is set
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
!
Mode setting
setting
Mode
oFF
Not setting
op1
Snow removal mode
op2
Rapid defrost mode
op3
Snow removal mode. + Rapid defrost mode.
Target pressure adjusting
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“op1” ~ “op4” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn8” Push the ‘
●
’ button
Target pressure is set
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“HEAT” , “COOL” Push the ‘
●
’ button
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
!
Setting
Mode
Purpose
Condensing
temperature
variation
Evaporating
temperature
variation
Heat
Cool
op1
Increase capacity
Increase capacity
-3 °C
+2 °C
op2
Decrease power
consumption
Increase capacity
-1.5 °C
-2 °C
op3
Decrease power
consumption
Decrease power
consumption
+2.5 °C
-4 °C
op4
Decrease power
consumption
Decrease power
consumption
-4.5 °C
-6 °C
Snow removal & rapid defrost
Mode setting method
IDU capacity adjusting
If the operation of indoor unit is more than 130%, the air flow is oper-
ated as low in the all indoor units.
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn7” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“on” ~ “oFF” Push the ‘
●
’ button
IDU capacity adjusting is set
CAUTION
• Ask an authorized technician to setting a function.
!
Comfort Operation
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn9” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“on” ~ “oFF” Push the ‘
●
’ button
Comfort Operation mode is set
CAUTION
• Ask an authorized technician to setting a function.
* If do not use a function, set an off-mode.
!
Step
Mode
OFF
Not setting
ON
Low capacity mode
Step
Mode
OFF
Not setting
ON
Changing the low pressure target in cooling