Test Run
ENGLISH
Installation Manual
67
Display
Title
Cause of Error
Outdoor unit related error
4
9
1
Outdoor unit Faulty IPM Temperature
Sensor
Outdoor unit IPM Temperature Sensor short/open
5
0
1
Omitting connection of R, S, T power of
Outdoor unit
Omitting connection of outdoor unit
5
1
1
Excessive capacity of indoor units
Excessive connection of indoor units compared to capacity
of Outdoor Unit
5
2
1
Transmission error : inverter PCB
’
Main PCB
Failing to receive inverter signal at main PCB of Outdoor
unit
5
3
1
Transmission error : indoor unit
’
main
PCB of Outdoor Unit
Failing to receive indoor unit signal at main PCB of
Outdoor Unit .
5
4
1
Reverse connection of R, S, T power of
Outdoor unit
Reverse connection or omitting connection of R, S, T
power of Outdoor unit
5
7
1
Outdoor unit Communication Error with
Inverter Controller
Outdoor unit Controller part cannot receive inverter control
signals (usually happens after on-boarding)
6
0
1
Inverter PCB EEPROM Error of Outdoor
Unit
Access Error of Inverter PCB of Outdoor unit
6
7
1
Outdoor unit Fan Lock
Restriction of Outdoor unit
6
9
1
Constant1 CT Sensor Error of Outdoor
Unit
Constant1 CT Sensor open or short of Outdoor unit
7
0
1
Constant2 CT Sensor Error of Outdoor
Unit
Constant2 CT Sensor open or short of Outdoor unit
7
3
1
Instant Over Current(Peak) of Outdoor unit
PFC
Instant Over Current(Peak) of Outdoor unit PFC
7
5
1
Outdoor unit Fan CT Sensor Error
Outdoor unit Fan CT Sensor open or short
7
6
1
Outdoor unit Fan DC Link High Voltage
Error
Outdoor unit Fan DC Link High Voltage Error
7
7
1
Outdoor unit Fan Over Current Error
Outdoor unit Fan Current is over 5A
7
9
1
Outdoor unit Fan Start Failure Error
Outdoor unit Fan First Position Sensing Failure
8
6
1
Outdoor unit Main PCB EEPROM Error
Communication Fail Between Outdoor unit Main MICOM
and EEPROM or omitting EEPROM
8
7
1
Outdoor unit Fan PCB EEPROM Error
Communication Fail Between Outdoor unit Fan MICOM
and EEPROM or omitting EEPROM