Lifting Method
ENGLISH
Installation Manual
13
Installation
The location of the Anchor bolts
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
• The outdoor unit supports at the bottom shall have width of at least 100mm under the unit°Øs legs before being fixed.
• The outdoor unit supports should have minimum height of 200mm.
• Anchor bolts must be inserted at least 75mm.
For outdoor units of
23kW or above should
not be supported only by
the corner supports.
At least 100mm
At least 100mm
At least 100mm
At least 100mm
730
760
65
65
Unit : mm
At least 65
At least 65
Chassis
Capacity(HP)
A (mm)
B (mm)
UX2
8~12
920
792