Pipe connections between indoor and outdoor unit
34
Outdoor Unit
Solo
-
Heat Pump
Vacuum Mode
This function is used for creating vacuum in the system after compressor replacement, ODU parts
replacement or IDU addition/replacement.
Outdoor unit PCB DIP switch ON
- DIP switch No. : 10, 12, 13
Vacuum mode setting
ODU V/V OPEN
Main EEV, SC EEV OPEN
IDU EEV OPEN
ODU power reset
Press the black button Main PCB (5 sec.)
Vacuum mode setting method
Vacuum mode cancellation method
Outdoor unit PCB DIP switch OFF
- DIP switch No. : 10, 12, 13
Power reset
Vacuum mode cancellation
CAUTION
ODU operation stops during vacuum mode. Compressor can't operate.