STANDARD | 113
Standard W
all-Mounted
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 59: ARNU363SVA4
Heating Capacity Table.
STANDARD WALL-MOUNTED
Heating Capacity Tables
ARNU363SVA4
Model No. /
Capacity Index
Outdoor
Air Temp.
Indoor Air Temperature (°F DB)
59
61
64
67
70
73
76
80
°F DB
°F WB
TC
TC
TC
TC
TC
TC
TC
TC
MBh
MBh
MBh
MBh
MBh
MBh
MBh
MBh
ARNU363SVA4 /
36.2
-21.6
-22.0
18.8
18.8
18.8
18.8
18.5
18.5
18.5
18.5
-17.1
-17.5
21.0
21.0
21.0
21.0
20.7
20.7
20.7
20.7
-12.6
-13
23.3
23.3
23.3
23.3
23.0
23.0
23.0
23.0
-7
-7.6
24.1
24.1
24.1
24.1
23.7
23.7
23.7
23.7
-4
-4.4
24.8
24.8
24.8
24.8
24.4
24.4
24.4
24.4
0
-0.4
25.5
25.5
25.5
25.5
25.5
25.2
25.2
25.2
5
4.5
28.9
28.5
28.1
28.1
28.1
28.1
28.1
28.1
10
9
30.0
30.0
30.0
29.6
29.6
29.6
29.6
29.6
15
14
31.8
31.8
31.8
31.8
31.8
31.8
31.5
31.1
20
19
33.7
33.7
33.7
33.7
32.9
32.9
32.4
32.0
25
23
35.2
35.2
35.2
35.2
35.2
34.4
34.0
32.4
30
28
35.9
35.9
35.9
35.9
35.9
35.2
34.0
32.4
35
32
37.0
37.0
37.0
37.0
36.6
35.9
34.0
32.4
40
36
38.5
38.5
38.5
38.5
37.0
35.9
34.0
32.4
45
41
40.0
40.0
40.0
38.9
37.0
35.9
34.0
32.4
47
43
41.4
41.1
40.7
38.9
37.0
35.9
34.0
32.4
50
46
44.4
42.6
40.7
38.9
37.0
35.9
34.0
32.4
55
51
45.3
42.9
40.7
38.9
37.0
35.9
34.0
32.4
60
56
45.3
42.9
40.7
38.9
37.0
35.9
34.0
32.4
Low ambient performance with LGRED° heat technology is included in Multi V 5 Air Source Units produced after February 2019.
TC: Total Capacity (MBh).
The System Combination Ratio must be between 50–130%.
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change
without notice.
Current certified ratings are available at
www.ahridirectory.org
.
For outdoor unit performance data, see the respective outdoor unit performance data
manuals on
https://lghvac.com/commercial
.