ART COOL
TM
| 31
Art Cool
TM
Mirror
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Electrical Wiring Diagram
SJ and SK Frames
Figure 13: ARNU053~153SJR4 and ARNU183-243SKR4 Wiring Diagram.
ART COOL MIRROR
PCB Connection
Purpose
Function
CN-POWER
AC power supply
AC Power line input for indoor controller
CN-MOTOR
Fan motor output
Motor output of BLDC
CN-EEV
EEV output
EEV control output
CN-U/D
Step motor
Step motor output
CN-DISP2
Display
Display of indoor status
CN-DISP1
Display
Display of indoor status
CN-CC
Dry contact
Dry contact connection
CN-EXT1
External ON / OFF controller
External ON / OFF controller connection
CN-485
Communication
Connection between indoor and outdoor units
CN-REMO
Remote controller
Remote control connection
CN-LEAK
Refrigerant leak detector
Refrigerant leak detector connection
CN-TH3
Float switch
Float switch connection
CN-TH1
Return air and inlet pipe thermistor
Return air and inlet pipe thermistor connection
CN-TH2
Outlet pipe thermistor
Outlet pipe thermistor connection
CN-PTC
Auxiliary heater
Auxiliary heater connection
CN-WF
Wi-Fi module
Wi-Fi module connection
Table 14: SJ and SK Frame Wiring Diagram Legend.
*To enable Generation 4 features, outdoor unit DIP switch no. 3 must be set to ON. Please refer to the Multi V 5, Multi V IV, Multi V Water IV, Multi V
S Engineering Manual for additional information.