72
ELECTRICAL WIRING
ENGLISH
Self-Diagnosis Function
Error Indicator
- This function indicates types of failure in self-diagnosis and occurrence of failure for air condi-
tion.
- Error mark is displayed on display window of indoor units and wired remote controller, and 7-
segment LED of outdoor unit control board as shown in the table.
- If more than two troubles occur simultaneously, lower number of error code is first displayed.
- After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
1st,2nd,3rd LED of 7-segment indicates error number, 4th LED indicates unit number.
Ex)
* Refer to the DX-Venitilation manual for DX-Venitilation error code.
Display
Title
Cause of Error
Indoor unit related error
0
1
-
Air temperature sensor of indoor unit
Air temperature sensor of indoor unit is open or short
0
2
-
Inlet pipe temperature sensor of indoor unit
Inlet pipe temperature sensor of indoor unit is open or short
0
3
-
Communication error : wired remote
controller
÷
indoor unit
Failing to receive wired remote controller signal in indoor
unit PCB
0
4
-
Drain pump
Malfunction of drain pump
0
5
-
Communication error : outdoor unit
÷
indoor unit
Failing to receive outdoor unit signal in indoor unit PCB
0
6
-
Outlet pipe temperature sensor of indoor
unit
Outlet pipe temperature sensor of indoor unit is open or
short
0
9
-
Indoor EEPROM Error
In case when the serial number marked on EEPROM of
Indoor unit is 0 or FFFFFF
1
0
-
Poor fan motor operation
Disconnecting the fan motor connector/Failure of indoor
fan motor lock
1
7
-
Inlet Air temperature sensor of FAU
Air temperature sensor of indoor unit is open or short
Outdoor unit related error
2
1
1 Master Outdoor Unit Inverter Compressor IPM Fault
Master Outdoor Unit Inverter Compressor Drive IPM Fault
2 Slave1 Outdoor Unit Inverter Compressor IPM Fault Slave1 Outdoor Unit Inverter Compressor Drive IPM Fault
3 Slave2 Outdoor Unit Inverter Compressor IPM Fault Slave2 Outdoor Unit Inverter Compressor Drive IPM Fault
4 Slave3 Outdoor Unit Inverter Compressor IPM Fault Slave3 Outdoor Unit Inverter Compressor Drive IPM Fault
2
2
1
Inverter Board Input Over Current(RMS) of
Master Outdoor Unit
Master Outdoor Unit Inverter Board Input Current excess
(RMS)
2
Inverter Board Input Over Current(RMS) of
Slave1 Outdoor Unit
Slave1 Outdoor Unit Inverter Board Input Current excess
(RMS)
3
Inverter Board Input Over Current(RMS) of
Slave2 Outdoor Unit
Slave2 Outdoor Unit Inverter Board Input Current excess
(RMS)
4
Inverter Board Input Over Current(RMS) of
Slave3 Outdoor Unit
Slave3 Outdoor Unit Inverter Board Input Current excess
(RMS)
Error No. of Compressor
Error No.
Error No. of Unit
Repeat