ELECTRICAL WIRING
63
ENGLISH
Checking the setting of outdoor units
Checking according to dip switch setting
- You can check the setting values of the Master outdoor unit from the 7 segment LED.
The dip switch setting should be changed when the power is OFF.
Checking the initial display
The number is sequentially appeared at the 7 segment in 5 seconds after applying the power.
This number represents the setting condition. (For example, represents R410A 30HP)
• Initial display order
• Example) A(B)RUN620LTE4
• Master Unit
• Slave Unit
Dip switch setting
Dip switch setting
ODU Setting
Slave 1
Slave 2
Slave 3
Order
No
Mean
①
8~20
Master model capacity
②
10~20
Slave 1 model capacity
③
10~20
Slave 2 model capacity
④
10~20
Slave 3 model capacity
⑤
8~80
Total capacity
⑥
1
Cooling Only
2
Heat Pump
3
Heat Recovery
⑦
38
380V model
46
460V model
22
220V model
⑧
1
LTE4
2
LTS4
①
②
③
④
⑤
⑥
⑦
⑧
18
16
14
14
62
2
38
1