ELECTRICAL WIRING
71
ENGLISH
Target pressure adjusting
mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn8” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“op1” ~ “op4” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn8” Push the ‘
●
’ button
Target pressure is set
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“HEAT” , “COOL” Push the ‘
●
’ button
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
!
Setting
mode
Purpose
Condensing
temperature
variation
Evaporating
temperature
variation
“Heat”
“Cool”
op1
Increase capacity
Increase capacity
-3 °C
+2 °C
op2
Decrease power consumption
Increase capacity
-1.5 °C
-2 °C
op3
Decrease power consumption Decrease power consumption
+2.5 °C
-4 °C
op4
Decrease power consumption Decrease power consumption
-4.5 °C
-6 °C
Содержание Multi V ABRUV100LTS4
Страница 86: ...86 ENGLISH ...
Страница 87: ......