51
ENGLISH
Display
Title
Cause of Error
2
6
*
Outdoor Unit Inverter Compressor Start Failure
The first start failure by Outdoor Unit Inverter Compressor
abnormality or Compressor locked
2
9
*
Outdoor Unit Inverter Compressor Over Current
Outdoor Unit Inverter Compressor Fault OR Drive Fault
3
2
*
Outdoor Unit Inverter Compressor1 High
Discharge Temperature
Outdoor Unit Inverter Compressor1 High Discharge Temperature
3
3
*
Outdoor Unit Inverter Compressor2 High
Discharge Temperature
Outdoor Unit Inverter Compressor2 High Discharge Temperature
3
4
*
High Pressure of Outdoor Unit
High Pressure of Outdoor Unit
3
5
*
Low Pressure of Outdoor Unit
Low Pressure of Outdoor Unit
4
0
*
Outdoor Unit Inverter Compressor CT Sensor Fault
Outdoor Unit Inverter Compressor CT Sensor open or short
4
1
*
Outdoor Unit Inverter Compressor1 Discharge
Temperature Sensor Fault
Outdoor Unit Inverter Compressor Discharge Temperature
Sensor open or short
4
2
*
Outdoor Unit Low Pressure Sensor Fault
Outdoor Unit Low Pressure Sensor open or short
4
3
*
Outdoor Unit High Pressure Sensor Fault
Outdoor Unit High Pressure Sensor open or short
4
4
*
Outdoor Unit Air Temperature Sensor Fault
Outdoor Unit Air Temperature Sensor open or short
4
5
*
Outdoor Unit Heat Exchanger Temperature Sensor
(Front side) Fault
Outdoor Unit Heat Exchanger Temperature Sensor(Front side)
open or short
4
6
*
Outdoor Unit Suction Temperature Sensor Fault
Outdoor Unit Suction Temperature Sensor open or short
4
7
*
Outdoor Unit Inverter Compressor2 Discharge
Temperature Sensor Fault
Outdoor Unit Inverter Compressor2 Discharge Temperature
Sensor open or short
4
9
*
Outdoor Unit Faulty IPM Temperature Sensor
Outdoor Unit IPM Temperature Sensor short/open
5
0
*
Omitting connection of R, S, T power of Outdoor
Unit
Omitting connection of outdoor unit
5
1
*
Excessive capacity of indoor units
Excessive connection of indoor units compared to capacity of
Outdoor Unit
5
2
*
Communication error : inverter PCB
’
Main PCB
Failing to receive inverter signal at main PCB of Outdoor Unit
5
3
*
Communication error : indoor unit
’
Main PCB of
Outdoor Unit
Failing to receive indoor unit signal at main PCB of Outdoor Unit.
5
7
*
Communication error : Main PCB
’
inverter PCB
Failing to receive signal main PCB at inverter PCB of Outdoor Unit
6
0
*
Inverter PCB EEPROM Error of Master Outdoor Unit
Access Error of Inverter PCB of Outdoor Unit
6
2
*
Outdoor Unit Inverter Heatsink High Temperature
System is turned off by Outdoor Unit Inverter Heatsink High
Temperature
6
5
*
Outdoor Unit Inverter Heatsink Temperature
Sensor Fault
Outdoor Unit Inverter Heatsink Temperature Sensor open or
short
6
7
*
Outdoor Unit Fan Lock
Restriction of Outdoor Unit
7
1
*
Inverter CT Sensor Error of Master Outdoor Unit
Inverter CT Sensor open or short of Outdoor Unit
7
5
*
Outdoor Unit Fan CT Sensor Error
Outdoor Unit Fan CT Sensor open or short
7
7
*
Outdoor Unit Fan Over Current Error
Outdoor Unit Fan Current is over 6 A
7
9
*
Outdoor Unit Fan Start Failure Error
The first start failure by Outdoor Unit Fan abnormality or Fan
locked
8
6
*
Outdoor Unit Main PCB EEPROM Error
Communication Fail Between Outdoor Unit Main MICOM and
EEPROM or omitting EEPROM
8
7
*
Outdoor Unit Fan PCB EEPROM Error
Communication Fail Between Outdoor Unit Fan MICOM and
EEPROM or omitting EEPROM
1
0
4
*
Communication Error Between Outdoor Unit and
Other Outdoor Unit
Failing to receive Slave Unit signal at main PCB of Outdoor Unit
1
0
5
*
Outdoor Unit Fan PCB Communication Error
Failing to receive fan signal at main PCB of Outdoor unit
1
0
6
*
Outdoor Unit Fan IPM Fault Error
Instant Over Current at Outdoor Unit Fan IPM
O
utdoor unit related error
Содержание Multi V 5 ARUM080LTE5
Страница 55: ......