47
ENGLISH
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn10” Push the ‘
●
’ button
High Efficiency Mode is set
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“on”,“oFF” Push the ‘
●
’ button
Mode Setting
Setting
Operation
time
Operating
time
Repeat
cycle
Detail of function
op1
Stop
+2hour
5minutes
2hour
After product stopped 2 hour, fan operating
5min(Repeated every 2 hours)
op2
stop
+5minutes
3minutes
Twice in
2 hour
after product stopped 5 minutes, fan
operating 3min (Limited to two times within 2
hours)
op3
stop
+5minutes
3minutes
1 time
after product stopped 2 hour, fan operating
5min(Repeated every 2 hours)
op4
Stop
+1minutes
1minutes
1 time
after product stopped 5 minutes, fan
operating 3min(when io module
connection/one-time operation)
op5
Stop
+1minutes
1minutes
Low
speed
after product stopped 1minutes, fan operating
1min(every time the product stops)
Function setting
Setting
Inverter (Hz)
oFF
-
op1
143 Hz
op2
135 Hz
op3
128 Hz
op4
120 Hz
op5
113 Hz
op6
105 Hz
op7
98 Hz
op8
90 Hz
op9
83 Hz
CAUTION
• Ask an authorized technician to setting a function.
• If use a function, first install a Central controller.
!
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn13” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“op1”~“op7” Push the ‘
●
’ button
ODU Fan Max. RPM Limit Mode is set
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn 12” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“op1”,“op9” Push the ‘
●
’ button
Cool & Heat Selection mode is set
ODU Fan Max. RPM Limit
Mode setting method
Compressor Max. Frequency Limit
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn11” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“op1”~“op5” Push the ‘
●
’ button
Auto Dust Removal Mode is set
Auto Dust Removal Mode
The ability to set reverse run outdoor fan to remove dust, heat
exchanger.
Mode setting method
High Efficiency Mode (Cooling Operation)
Target low pressure will change according to ODU temperature during
the cooling operation.
Mode setting method