36
ENGLISH
HR unit
Master
Outdoor Unit
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
3
4
3
4
3
4
In case of Heat Recovery System
Between Indoor and Master Outdoor unit
The GND terminal at the
main PCB is a ‘-’ terminal
for dry contact, it is not
the point to make ground
connection.
WARNING
• Indoor Unit ground wires are required for preventing electrical
shock accident during current leakage, Communication disorder by
noise effect and motor current leakage (without connection to
pipe).
• Don't install an individual switch or electrical outlet to disconnect
each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an
integrated manner because this system consists of the equipment
utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase,
momentary blackout or the power goes on and off while the
product is operating, attach a reversed phase protection circuit
locally. Running the product in reversed phase may break the
compressor and other parts.
!
Series outdoor units
When the power source is connected
In series between the units.
R S T N
Switch
Fuse
L
N
Communication Line
(2 Wires Cable)
Power Line
(4 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
[Slave1]
[Slave2]
[Slave3]
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
HR unit
Outdoor
Power supply
(3 Ø 4wires)
Indoor
Power supply
(1 Ø 2wires)
(Main Switch)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
In case of Heat
Recovery System
Frequency
Voltage range(V)
Outdoor
Indoor
60 Hz
380 V
220 V
50 Hz
380-415 V 220-240 V
Example) Connection of transmission wire
[BUS type]
[STAR type]
When the power source is supplied to Each outdoor unit individually.
R S T N
Switch
Fuse
L
N
Communication Line
(2 Wires Cable)
Power Line
(4 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
[Slave1]
[Slave2]
[Slave3]
R S T N
Switch
Fuse
R S T N
Switch
Fuse
R S T N
Switch
Fuse
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
HR unit
Outdoor
Power supply
(3 Ø 4wires)
Indoor
Power supply
(1 Ø 2wires)
(Main Switch)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
In case of Heat
Recovery System
Frequency
Voltage range(V)
Outdoor
Indoor
60 Hz
380 V
220 V
50 Hz
380-415 V 220-240 V
HR unit
Slave1
Outdoor Unit
Master
Outdoor unit
Slave2
Outdoor Unit
Slave3
Outdoor Unit
3
4
3
4
3
4
Master
Outdoor Unit
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
In case of Heat Recovery System
Between Indoor and Master Outdoor unit
The communication cables between indoor unit and master outdoor
unit are possible to connect with BUS type or STAR type.
The GND terminal at the main PCB is a ‘-’ terminal for dry contact.
It is not the point to make ground connection.
- Make sure that terminal number of master and slave outdoor units
are matched.(A-A, B-B)
WARNING
• Indoor Unit ground wires are required for preventing electrical
shock accident during current leakage, Communication disorder by
noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect
each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an
integrated manner because this system consists of the equipment
utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase,
momentary blackout or the power goes on and off while the
product is operating, attach a reversed phase protection circuit
locally.
Running the product in reversed phase may break the compressor
and other parts.
!
WARNING
When the total capacity is over than as follow, the power source
do not use in series between the units.
The First terminal block could be burnt out.
!
- Connection of communication
cable must be installed like
below figure between indoor
unit to outdoor unit.
- Abnormal operation can be
caused by communication
defect, when connection of
communication cable is installed
like below figure(STAR type).