ELECTRICAL SYSTEM INSTALLATION
NJ/NK Chassis DIP Switch Settings
Table 20: NJ/NK Frame DIP Switch Settings.
DIP Switch Settings for Indoor Unit PCB
To operate the indoor unit without Internal Electric Heater, Dip switch 1, 2, 6, 8 must be set OFF.
To operate the indoor unit with Internal Electric heater, Dip switch 6 must be set ON.
• SW6 ON: Automatic Heater operation: Heater operates automatically.
• SW6 OFF: Manual Heater operation: Owner’s involvement is required for on/off operation.
If you operate the indoor unit with Internal Electric heater with Dip switch 5, note the following:
• SW5 ON: Fan operates continuously. During defrosting or oil return operation, uninterrupted heating can be attained, as a result of continu-
ous heater and fan operation.
• SW5 OFF: Fan discontinuous operation. There would be reduction in heating capacity while defrosting or oil return operation.
Dip
Switch
Function
Off
On
Description
SW1
COMMUNICATION
Off (default)
_
_
SW2
CYCLE
Off (default)
_
_
SW3
GROUP CONTROL
Master
Slave
Group control setting using 7-Day Programmable Controller; selects Master/
Slave on each indoor unit.
SW4
DRY CONTACT
MODE
Variable
Auto
Sets operation mode for optional Dry Contact accessory.
1. Variable: Auto or Manual Mode can be set through 7-Day Programmable
Controller or Wireless Remote Controller (factory default setting is Auto if
there is no setting).
2. Auto: For Dry Contact, it is always Auto mode.
SW5
CONTINUOUS FAN
Off
On
Selects continuous fan for ducted indoor units.
1. On: Indoor unit fan will always operate at a set fan speed, except when the
system is off, or the outdoor unit is in defrost mode (when the outdoor unit is
in defrost mode, the fan will operate at super low fan speed).
2. Off: Indoor unit fan speed can be changed by on / off.
SW6
HEATER INTERLOCK
Off
On
Selects heater interlock function for Vertical Air Handling units.
1. On: Automatic (heater will automatically operate during heating mode).
2. Off: Manual (heater needs to be manually turned on during heating mode).
SW7
Off
SW8
Off