![LG LS090HEV Скачать руководство пользователя страница 21](http://html.mh-extra.com/html/lg/ls090hev/ls090hev_installation-manual_213201021.webp)
21
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
general data
Model Number
Nom. Tons
Compressor
Qty
Compressor
(A) Cool/Heat
Fan Qty
ODU Fan (A) IDU Fan (A)
MCA (A)
MOP (A)
LSU091HSV3
3/4
1
8.7/8.7
1
0.40
0.4
10
15
LSU121HSV3
1
1
8.7/8.7
1
0.40
0.4
10
15
LSU181HSV3
1-1/2
1
15.4/15.4
1
0.25
0.4
19
25
LSU240HSV3
1-3/4
1
15.4/15.4
1
0.25
0.5
19
25
Table 6:
Single Zone High Efficiency Indoor Unit Electrical Data
Model Number
Nom. Tons
Compressor
Qty
Compressor
(A) Cool/Heat
Fan Qty
ODU Fan (A) IDU Fan (A)
MCA (A)
MOP (A)
LSU307HV3
2-1/2
1
15.4/15.4
1
0.25
0.5
19
25
LSU360HV3
2-3/4
1
15.4/15.4
1
0.25
0.5
19
25
Table 7: Single Zone Standard Indoor Unit Electrical Data
Model Number
Nom. Tons
Compressor
Qty
Compressor
(A) Cool/Heat
Fan Qty
ODU Fan (A) IDU Fan (A)
MCA (A)
MOP (A)
LSU240HLV
1-3/4
1
17.3/17.3
1
0.25
0.5
23
35
LSU300HLV
2-1/2
1
17.3/17.3
1
0.25
0.5
23
35
LSU360HLV
2-3/4
1
17.3/17.3
1
0.25
0.5
23
35
Table 8: Single Zone Extended Pipe Indoor Unit Electrical Data
Electrical
Unit Model Nos. Nom. Tons
Compressor
Qty
Compressor
(A) Cool/Heat
Fan Qty
ODU Fan (A) IDU Fan (A)
MCA (A)
MOP (A)
LSU090HEV
3/4
1
6.8/6.8
1
0.5
0.5
9
15
LSU120HEV
1
1
6.8/6.8
1
0.5
0.5
9
15
LSU180HEV
1 1/2
1
8.68/9.28
1
0.4
0.4
12
20
LSU240HEV
2
1
10.8/9.6
1
0.48
0.48
14
20
Table 9: 208-230V, 60Hz, 1-Phase Single Zone Mega Indoor Unit Electrical Data
Table 10: 115V, 60Hz, 1-Phase Single Zone Mega 115V Indoor Unit Electrical Data
Unit Model Nos. Nom. Tons
Compressor
Qty
Compressor
(A) Cool/Heat
Fan Qty
ODU Fan (A) IDU Fan (A)
MCA (A)
MOP (A)
LSU090HXV
3/4
1
10/10
1
0.4
0.5
13.5
20
LSU120HXV
1
1
10/10
1
0.4
0.5
13.5
20
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MSC = Maximum Starting Current.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated
as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest
standard fuse size.