Electrical System Installation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ELECTRICAL SYSTEM INSTALLATION
Controller Options
Handheld Remote Controller
Single Zone Art Cool Premier Wall Mounted systems include a wireless handheld remote controller (Part No.
AKB74955602). Optional LG-suppled wired controllers are available. See “Functions, Controls, Options”in the
Engineering Manual, or contact an LG representative for more information.
Wireless Handheld Remote Controller features:
• Display Panel: Displays operation conditions.
• On / Off Button: Turns system operation on and off.
• Mode Button: Selects the operation mode: Cooling,
Heating, Auto, Dry (Dehumidification), or Fan.
• Temp Up / Down Buttons: Adjusts the desired room
temperature in the different modes.
• Fan Speed Button: Sets desired fan speed.
• Reset: Initializes the handheld remote control set-
tings.
Dry Contact
A Dry Contact can also be connected to the Art Cool Premier indoor
unit using the CN-CC connection on the indoor unit PCB. The Dry
Contact DC is shipped with a specific connector that is used to con-
nect to the indoor unit.
Central Controller
Additionally, Single Zone Art Cool Premier systems can be con-
nected to a central controller if a PI-485 VNet Accessory is installed
in the outdoor unit. See the Central Controller manual for wiring
specifications.
Figure 84: Schematic of a Single Zone System When the Wiring is GREATER THAN 130 Feet.
Wired Controller Connections
Optional controllers (see the Single Zone Art Cool Premier Wall-Mounted Engineering Manual, or contact an
LG representative for more information) connect to the Single Zone Art Cool Premier Piping Wall-Mounted
indoor unit in one of two different ways.
1. LG Wired Remote Extension Cable with Molex plug (PZCWRC1; sold separately) that connects to the CN-
REMO terminal on the indoor unit PCB.
2. Field-supplied controller cable that connects to the indoor unit
terminal block (must be at least UL2547 or UL1007, and at least
FT-6 rated if local electric and building codes require plenum
cable usage). Communication cable from indoor unit to remote
controller(s) is to be 22 AWG, 3-conductor, twisted, stranded,
unshielded. Wiring must comply with all applicable local and
national codes.
Figure 85: AKB74955602
Wireless Handheld Remote
Controller.
:KHQXVLQJ¿HOGVXSSOLHGFRQWUROOHUFDEOHPDNHVXUHWRFRQQHFWWKH\HOORZWR\HOORZFRPPXQLFDWLRQVZLUHUHGWRUHG9SRZHUZLUHDQGEODFN
to black (ground wire) terminals from the remote controller to the indoor unit terminal blocks.
Verify the connectors are properly inserted.
C/BOX Cable (Plug type)
Extension cable
To Indoor Unit
CN-REMO
Terminal
TEMP
FAN
SPEED
OPER
MODE
Figure 86: PZCWRC1 LG Wired Remote Extension Cable.
Figure 87: Wired Controller Connections on the Indoor Unit Terminal
Block.
Power
Supply
1(L1) (Power, L)
2(L2) (Neutral, N)
G (Ground)
Power Flow: L
ĺ
N
Diagram is an example of communication and power
cables when the wiring is GREATER THAN 130 feet.
Terminals may be labeled differently depending on the model.
Outdoor and Indoor Unit appearances may vary depending on the model.
Communication Flow: Comm
ĺ
N
3 (Communications)
GREATER THAN 130 feet: Must Separate Communications and Ground (G) Cable from the Power
(1[L1]) and Neutral (2[L2]) Cable at Least Two (2) Inches.
At Least Two (2) Inches
Display
Button
Screen
*
*
*
Reset
Indoor Unit Terminal
BR BL
RD
GR/YL
&RQQHFWLRQVDQG6SHFL¿FDWLRQV&RQWUROOHU2SWLRQV