GENERAL DATA
Electrical
Nominal
Tons
Unit Model
Number
Hertz Voltage Voltage Range
(Min. to Max.) MCA MOP
Compressor
Qty.
Compressor Motor
RLA
Outdoor Fan
Motor
Indoor Fan
Motor
Cooling Heating
W
FLA
W
FLA
3/4
LA090HYV3
60 208 -230
187 - 253
11.2
15
1
8.3
8.3
85
0.4
58
0.4
1
LA120HYV3
11.2
15
1
8.3
8.3
85
0.4
58
0.4
1-1/4
LA150HYV3
19.0
30
1
14.41
14.41
124
0.4
58
0.5
1-1/2
LA180HYV3
19.0
30
1
14.41
14.41
124
0.4
58
0.5
2
LA240HYV3
19.0
30
1
14.41
14.41
124
0.4
58
0.5
Table 2: Art Cool Premier Electrical Data
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.