Display Function
1. Heating Model
2. Cooling Model
Self-diagnosis Function
■
Error Indicator
• The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
• Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
• If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
• After error occurrence, if error is released, error LED is also released simultaneously.
• To operate again on the occurrence of error code 12, be sure to pull out power cord and then re-insert.
• Having or not of error code is different from Model.
-20-
1
(3times)
3sec
3sec
(5times)
3sec
(twice)
3sec
3sec
(once)
3sec
3sec
3sec
2
3
5
8
Error
Code
Error LED
(Indoor body operation LED)
Error contents
SVC check point
• Indoor suction temperature
thermistor open/short.
• Indoor pipe temperature
thermistor open/short.
• Indoor TH ass'y check
• Outdoor TH ass'y
check
• Resetting of remocon
operating mode
• Communication
line/circuit check
• Outdoor suction temperature
thermistor open/short.
• Outdoor pipe temperature
thermistor open/short.
• Abnormal operation of multi
product.
(Simultanueous operation of
cooling and heating)
• Indoor fan lock
• Poor communication
• Check indoor fan
motor and outdoor
PCB ass'y
• Cooling, Soft Dry, Fan, Heating
• Cooling, Soft Dry, Fan
• Sleep Mode
• Sleep Mode
• Timer Mode
• Timer Mode
• Hot-start, Defrost
Operation Indicator
Timer Indicator
Sleep Timer Indicator
Defrost Indicator
Operation Indicator
Timer Indicator
Sleep Timer Indicator
Compressor on Indicator
OUT
DOOR
Содержание L2-C243AL1
Страница 52: ... 52 Electronic Control Device 1 Indoor MAIN P C B ASM ...
Страница 53: ... 53 2 Outdoor MAIN P C B ASM ...
Страница 54: ... 54 3 Display Ass y ...
Страница 55: ... 55 Schematic Diagram 1 Indoor ...
Страница 56: ... 56 2 Outdoor ...
Страница 67: ...P No 3828A20097A July 2005 Printed in Korea ...