Troubleshooting
67
Troubleshoo
ting
4
P539
Grid Relay8
Grid relay is not operable (N-2)
Automatically restart
within a Minute
P540
SDSP Detection
The sub-processing unit in the
product is in fault
Automatically restart
within a Minute
P541
Fan Detection
The cooling fan in the product is in
fault
Automatically restart
within a Minute
Battery Fault (Single)
B101 Cell Over Voltage
Warning
Cell Voltage level of battery cell is
higher than 4.25V
Automatically restart
within a Minute
B102 Cell Under Voltage
Warning
Cell Voltage level of battery cell is
lower than 2.8V
Automatically restart
within a Minute
B103 Cell Voltage Imbalance
Warning
Cell Voltage differences between
the battery cells are higher than
300mV
Automatically restart
within a Minute
B104 Pack Over Voltage
Warning
PackVoltage level of battery pack
is higher than 236V
Automatically restart
within a Minute
B105 Pack Under Voltage
Warning
Pack Voltage level of battery pack
is lower than 166V
Automatically restart
within a Minute
B106 Over Charge Current
Warning
Current level of the battery is
higher than 20.6A
Automatically restart
within a Minute
B107 Over Discharge
Current Warning
Current level of the battery is
lower than 20.6A
Automatically restart
within a Minute
B108 Over Temperature
warning
The battery temperature is higher
than 45°C
Automatically restart
within a Minute
B109 Under Temperature
warning
The battery temperature is lower
than -10°C
Automatically restart
within a Minute
B110 Temperature
Deviation Warning
Temperature differences between
the batteries are over 5°C
Automatically restart
within a Minute
B301 Cell Over Voltage
Fault
Cell Voltage level of battery cell is
higher than 4.3V
Contact service center
B302 Cell Over Voltage 2nd
Protection
Cell Voltage level of battery cell is
higher than 4.4V
Contact service center
B303 Cell Under Voltage
Fault
Cell Voltage level of battery cell is
lower than 2.6V
Contact service center
Содержание D005KD1N111
Страница 84: ......
Страница 97: ...End user 2 4 1 1 1 3 13 3 8 Accept terms Owner checks Select All and select AGREE ...
Страница 113: ...Appendix Installer 29 3 9 f Select OK button Installer can check that another installer has been registered like below ...
Страница 115: ...Appendix Installer 31 5 9 Installer terms New installer must select the 2 boxes I agree and the button Submit ...
Страница 119: ...Appendix Installer 35 9 9 f Click Company Information Installer can check that a subsidiary has been registered f ...
Страница 120: ......
Страница 204: ......
Страница 217: ...Endverbraucher 2 4 1 1 1 3 13 3 8 Annahme der Geschäftsbedingungen Der Kunde wählt Alle auswählen und ZUSTIMMEN ...
Страница 240: ......
Страница 324: ......
Страница 360: ......
Страница 444: ......
Страница 457: ...Eindgebruiker 2 4 1 1 1 3 13 3 8 Voorwaarden accepteren De eigenaar schakelt Alles selecteren in en kiest ACCEPTEREN ...
Страница 480: ......