13. Installation
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually
according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the
terminal no. are the same as those of the indoor unit.)
• The circuit diagram is a subject to change without notice.
• The earth wire should be longer than the common wires.
• When installing, refer to the circuit diagram on the chassis cover.
• Connect the wires firmly so that they may not be pulled out easily.
• Connect the wires according to color codes, referring to the wiring diagram.
The power cord connected to the outdoor unit should be complied with IEC 60245 or HD 22.4 S4.
The power connecting cable connecting the indoor and outdoor unit should be complied with IEC 60245 or
HD 22.4 S4.
GN/YL
20mm
10
±
3mm
GN/YL
20mm
10
±
3mm
Insert the connecting cable through the bottom side of indoor unit and connect the cable (You can see detail
contents in 'Connecting the cables' section)
(1) Open the Front Grille
(2) Support the Front Grille with supporter
(3) Open the Control Cover
(4) Connect the connecting cable
h
Field wiring shall be done such that the current carrying conductors become taut before the earthing
conductor if the cord slips out of the cord anchorage.
Control Cover
1(L) 2(N) 3(C)
5k ~ 12kBtu
1.0
Cable Type(B)
H07RN-F
NORMAL CROSS -
SECTIONAL AREA
Capacity (Cooling)
(mm
2
)
5k ~ 12kBtu
1.0
Cable Type(B)
H07RN-F
NORMAL CROSS
-SECTIONAL AREA
Capacity (Cooling)
(mm
2
)
Connecting the Cables