82
_
Inverter Single-60Hz(R410A)
Inverter Single
Inverter Single
7. Capacity tables
°CDB
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
16.0
18.0
20.0
21.0
22.0
24.0
Outdoor Air Temperature : °CWB
-10
-5
0
6
10
15
Indoor Air
Temperature (°C)
AS-W122B1U0
3.16 0.76 3.43 0.79 3.66 0.85 4.07 0.91 4.30 0.95 4.66 1.01
3.16 0.78 3.43 0.82 3.66 0.88 4.04 0.94 4.24 0.97 4.65 1.02
3.16 0.80 3.44 0.84 3.65 0.90 4.00 0.96 4.21 0.98 4.66 1.03
3.16 0.81 3.44 0.85 3.64 0.91 3.97 0.96 4.21 0.99 4.63 1.03
3.16 0.82 3.43 0.87 3.63 0.92 3.95 0.97 4.21 1.00 4.59 1.03
3.13 0.84 3.39 0.89 3.61 0.95 3.91 0.99 4.14 1.01 4.53 1.04
°CDB
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
16.0
18.0
20.0
21.0
22.0
24.0
Outdoor Air Temperature : °CWB
-10
-5
0
6
10
15
Indoor Air
Temperature (°C)
AS-W122BRW0, AS-W122B4A0
3.16 0.84 3.43 0.87 3.66 0.94 4.07 1.00 4.30 1.05 4.66 1.11
3.16 0.86 3.43 0.90 3.66 0.97 4.04 1.03 4.24 1.07 4.65 1.13
3.16 0.88 3.44 0.93 3.65 0.99 4.00 1.05 4.21 1.08 4.66 1.13
3.16 0.89 3.44 0.94 3.64 1.00 3.97 1.06 4.21 1.09 4.63 1.13
3.16 0.90 3.43 0.95 3.63 1.02 3.95 1.07 4.21 1.10 4.59 1.13
3.13 0.93 3.39 0.98 3.61 1.04 3.91 1.09 4.14 1.11 4.53 1.14
°CDB
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
16.0
18.0
20.0
21.0
22.0
24.0
Outdoor Air Temperature : °CWB
-10
-5
0
6
10
15
Indoor Air
Temperature (°C)
AS-W182C2U0, AS-W182CRW0, AS-W182C4A0
4.98 1.31 5.40 1.37 5.77 1.48 6.40 1.58 6.77 1.64 7.34 1.75
4.98 1.35 5.41 1.41 5.77 1.52 6.36 1.62 6.68 1.67 7.32 1.77
4.97 1.38 5.41 1.45 5.75 1.56 6.30 1.65 6.64 1.70 7.33 1.78
4.97 1.40 5.41 1.47 5.74 1.58 6.26 1.67 6.64 1.71 7.29 1.78
4.98 1.42 5.41 1.49 5.72 1.60 6.21 1.68 6.63 1.72 7.23 1.78
4.93 1.46 5.34 1.54 5.68 1.64 6.17 1.71 6.52 1.74 7.14 1.80
°CDB
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
16.0
18.0
20.0
21.0
22.0
24.0
Outdoor Air Temperature : °CWB
-10
-5
0
6
10
15
Indoor Air
Temperature (°C)
AS-W242C2U0, AS-W242CRW0, AS-W242C4A0
6.68 1.85 7.24 1.94 7.73 2.08 8.58 2.23 9.07 2.32 9.84 2.47
6.67 1.90 7.25 2.00 7.73 2.14 8.52 2.28 8.95 2.36 9.81 2.50
6.66 1.95 7.25 2.05 7.71 2.20 8.44 2.33 8.89 2.40 9.83 2.51
6.66 1.98 7.25 2.08 7.69 2.23 8.39 2.35 8.89 2.42 9.76 2.52
6.67 2.00 7.25 2.11 7.67 2.26 8.33 2.37 8.88 2.43 9.68 2.52
6.60 2.06 7.16 2.17 7.61 2.31 8.26 2.41 8.73 2.45 9.57 2.54
Symbol
Notes
AFR : Air Flow Rate
[m
3
/min]
1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry Bulb Temperature
[°C]
2. Indicates nominal maximum capacity.
WB : Wet Bulb Temperature
[°C]
3. Direct interpolation is permissible. Do not extrapolate
TC : Total Capacity
[kW]
4. Capacities are based on the following conditions:
PI : Power Input
[kW]
- Interconnecting Piping Length 7.5m
(Comp.+ Indoor fan motor + Outdoor fan motor)
- Level Difference of Zero.
- Outdoor air : 85%RH. However, the condition on nominal capacity
is 7°CDB/6°CWB