8. Capacity coefficient factor
Notes
h
Equivalent pipe length = actual pipe number of band x 0.3
h
Additional Refrigerant Charge
Example: For Model No. AS-W126HDW0 having 15m pipe length, additional refrigerant to be charged is
(15-7) x 20 = 160g
* Refer to the specification for the maximum pipe length of each model.
* Libero R (2.5kW , 3.5kW)
Additional refrigerant must be charged after 12.5 m (there is no need to charge till 12.5 m based on reliability)
Model No.
Max. Pipe
Length(m)
Ⓐ
Max. Elevation
(m)
Ⓑ
Additional
Refrigerant[g/m(oz/ft)]
CAUTION:
• Capacity is based on standard length and
maximum allowance length is on the basis
of reliability.
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
AS-W092HDW0
15
7
20(0.22)
AS-W122HDW0
15
7
20(0.22)
AS-W092BRW0
15
7
20(0.22)
AS-W122BRW0
15
7
20(0.22)
AS-W092B4A0
15
7
20(0.22)
AS-W122B4A0
15
7
20(0.22)
AS-Q092BRW0
15
7
10(0.11)
AS-Q122BRW0
15
7
10(0.11)
AS-Q092B4A0 15
7
10(0.11)
AS-Q122B4A0 15
7
10(0.11)
AS-W092B1U0
20
10
20(0.22)
AS-W122B1U0
20
10
20(0.22)
AS-Q182CRW0
20
7
20(0.22)
AS-Q242CRW0
20
7
20(0.22)
AS-Q182C4A0 20
7
20(0.22)
AS-Q242C4A0 20
7
20(0.22)
AS-W182C2U0
20
15
20(0.22)
AS-W242C2U0
30
15
35(0.37)
AS-W182CRW0
20
15
20(0.22)
AS-W242CRW0
30
15
35(0.37)
AS-W182C4A0 20
15
20(0.22)
AS-W242C4A0 30
15
35(0.37)
US-Q092WSZ2
15
7
20(0.22)
US-Q122BSZ2
15
7
20(0.22)
US-Q182CSZ2
20
10
30(0.32)
US-Q242CSZ2
20
10
30(0.32)
US-W092WSZ2
15
7
20(0.22)
US-W122BSZ2
15
7
20(0.22)
US-W182CSZ2
20
10
30(0.32)
US-W242CSZ2
20
10
30(0.32)
AS-Q092BRZ0
15
7
10(0.11)
AS-Q122BRZ0
15
7
10(0.11)
AS-Q182CRZ0
20
7
20(0.22)
AS-Q242CRZ1
20
10
30(0.32)
AS-W092BRZ0
15
7
20(0.22)
AS-W122BRZ0
15
7
20(0.22)
AS-W182CRZ0
20
15
30(0.32)
AS-W242CRZ1
20
10
30(0.32)