Outside units Information
8
Outside Unit
Outside units Information
Power Supply: Outside Unit (3Ø, 380 ~ 415V, 50Hz)
■
Heat pump
Unit
System(HP)
Model
Product Charge
kg
CF(Correction Factor)
kg
Max. Connectable No. of Indoor Units
Net Weight
kg
Dimension(W x H x D)
mm
inch
Refrigerant
Liquid(mm/inch)
Connecting Pipes
Gas(mm/inch)
Water
Inlet
Connecting Pipes
Outlet
Drain Outlet
Range of Operation
Cooling(
°
C)
Water Temp.
Heating(
°
C)
1 Unit
2 Unit
08
10
20
30
ARWB80LA2
ARWB100LA2
ARWB200LA2
ARWB300LA2
ARWB80LA2
ARWB100LA2
ARWB200LA2
ARWB200LA2
ARWB100LA2
7.3
7.3
8.8
7.3+8.8
1.5
1.5
3
4.5
13
16
32
49
170
170
238
170 + 238
772 x 1,120 x 547
772 x 1,120 x 547
772 x 1,120 x 547
(772 x 1,120 x 547) x 2
30.4 x 44.1 x 21.5
30.4 x 44.1 x 21.5
30.4 x 44.1 x 21.5
(30.4 x 44.1 x 21.5) x 2
9.52(3/8)
9.52(3/8)
12.7(1/2)
19.05(3/4)
22.2(7/8)
22.2(7/8)
28.58(1 1/8)
34.9(1 3/8)
PT32A (internal thread)
PT32A (internal thread)
PT40A (internal thread) PT32A + PT40A (internal thread)
PT32A (internal thread)
PT32A (internal thread)
PT40A (internal thread) PT32A + PT40A (internal thread)
20mm (internal thread)
20mm (internal thread)
20mm (internal thread)
20mm (internal thread)
10 ~ 45
10 ~ 45
10 ~ 45
10 ~ 45
10 ~ 45
10 ~ 45
10 ~ 45
10 ~ 45
Unit
System(HP)
Model
Product Charge
kg
CF(Correction Factor)
kg
Max. Connectable No. of Indoor Units
Net Weight
kg
Dimension(W x H x D)
mm
inch
Refrigerant
Liquid(mm/inch)
Connecting Pipes
Gas(mm/inch)
Water
Inlet
Connecting Pipes
Outlet
Drain Outlet
Range of Operation
Cooling(
°
C)
Water Temp.
Heating(
°
C)
2 Unit
3 Unit
40
50
60
ARWB400LA2
ARWB500LA2
ARWB600LA2
ARWB200LA2
ARWB200LA2
ARWB200LA2
ARWB200LA2
ARWB200LA2
ARWB200LA2
ARWB100LA2
ARWB200LA2
8.8+8.8
7.3+8.8+8.8
8.8+8.8+8.8
6
7.5
9
64
64
64
(238) x 2
170 + (238) x 2
(238) x 3
(772 x 1,120 x 547) x 2
(772 x 1,120 x 547) x 3
(772 x 1,120 x 547) x 3
(30.4 x 44.1 x 21.5) x 2
(30.4 x 44.1 x 21.5) x 3
(30.4 x 44.1 x 21.5) x 3
19.05(3/4)
19.05(3/4)
19.05(3/4)
41.3(1 5/8)
41.3(1 5/8)
41.3(1 5/8)
PT40A + PT40A (internal thread)
PT32A + PT40A + PT40A (internal thread)
PT40A + PT40A + PT40A (internal thread)
PT40A + PT40A (internal thread)
PT32A + PT40A + PT40A (internal thread)
PT40A + PT40A + PT40A (internal thread)
20mm (internal thread)
20mm (internal thread)
20mm (internal thread)
10 ~ 45
10 ~ 45
10 ~ 45
10 ~ 45
10 ~ 45
10 ~ 45
•
Ratio of the running Indoor Units to the Outside: Within 10 ~ 100%
•
A combination operation over 100% cause to reduce each indoor unit capacity.
■
Combination Ration(50~200%)
Notes:
* We can guarantee the operation only within 130% Combination.
If you want to connect more than 130% combination, please contact us and discuss the require-
ment like below.
1) If the operation of indoor unit is more than 130%, low airflow operation is recommended in all
the indoor units.
2) If the operation of indoor unit is more than 130%, additional refrigerant is needed according to
the
Ä
headquarter guidance.
3)Over 130%, capacity is same as capacity of 130%, Same remark is valid for power input.
Outside Number
Connection Capacity
Single outside units
200%
Double outside units
160%
Triple outside units
130%