72
Outside Unit
Electrical Wiring
Outside unit Dry Contact installation and connection
Mode setting without Cool/Heat Selector
•
Connect wires as below figure at the hole of backside of Outside Unit Dry Contact.
•
Insert the wire in the connection hole pushing the "Push" button.
•
Setting Main PCB Dip SW of Master Outside Unit.
In case of no Cool/Heat Selector, connect signal terminal block as below figure And description.
Connect signal terminal block as below figure and description.
- How to set mode without Cool/Heat Selector
•
Cooling Mode Setting
➀ ➔
GND Connection
➁ ➔
Off (Open)
•
Heating Mode Setting
➀ ➔
GND Connection
➁ ➔
GND Connection
•
Fan Mode Setting
➀ ➔
Off (Open)
➁ ➔
GND Connection
Mode Change
Push Button
Heating
Outdoor Unit
Fan
Cooling
GND
GND
GND