4. Electric Characteristics
15
MULTI V S
Outdoor Unit
Product Data
4.2 3 Phase / Heat Pump
■
50Hz
■
60Hz
Model
Unit
Power Supply
COMP
OFM
Hz
Volts
Voltage-range
MCA
TOCA
MFA
MSC
RLA(Cooling)
RLA(Heating)
kW
FLA
4 HP
50
380-415
Min.:342, Max.:456
12.5
17.0
20
-
4.3
3.3
0.35
1.0
5 HP
50
380-415
Min.:342, Max.:456
14.4
17.0
20
-
6.1
5.5
0.35
1.0
6 HP
50
380-415
Min.:342, Max.:456
16.1
17.0
20
-
7.0
6.8
0.35
1.0
8 HP
50
380-415
Min.:342, Max.:456
21.3
24.0
30
4.0
12.1
9.8
0.35
1.0
10 HP
50
380-415
Min.:342, Max.:456
26.3
35.0
30
4.5
16.5
10.4
0.50
2.8
12 HP
50
380-415
Min.:342, Max.:456
32.5
35.0
35
4.5
20.9
16.2
0.50
2.8
Model
Unit
Power Supply
COMP
OFM
Hz
Volts
Voltage-range
MCA
TOCA
MFA
MSC
RLA(Cooling)
RLA(Heating)
kW
FLA
4 HP
60
380
Min.:342, Max.:418
12.5
17.0
20
-
4.3
3.3
0.35
1.0
5 HP
60
380
Min.:342, Max.:418
14.4
17.0
20
-
6.1
5.5
0.35
1.0
6 HP
60
380
Min.:342, Max.:418
16.1
17.0
20
-
7.0
6.8
0.35
1.0
8 HP
60
380
Min.:342, Max.:418
21.3
24.0
30
4.0
12.1
9.8
0.35
1.0
10 HP
60
380
Min.:342, Max.:418
26.3
35.0
30
4.5
16.5
10.4
0.50
2.8
12 HP
60
380
Min.:342, Max.:418
32.5
35.0
35
4.5
20.9
16.2
0.50
2.8
Note
1. Voltage supplied to the unit terminals should be within the minimum and maximum
range.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MSC means the Max. current during the starting of compressor.
4. MSC and RLA are measured as the compressor only test condition.
5. OFM are measured as the outdoor unit test condition.
6. TOCA means the total over current value of each outdoor unit.
7. Select the wire size based on the larger value among MCA or TOCA.
8. MFA is recommended fuse amps.
9. TOCA is minimum required amperes for selecting the circuit breaker and ground fault
circuit interrupter. Please select the circuit breaker size equal or greater than TOCA.
All installation site must require attachment of an earth leakage breaker.[Circuit
breaker type is ELCB (Earth Leakage Circuit Breaker)].
10.Select the electrical equipment of combination unit according to the electrical
characteristics of individual unit.
Symbols
MCA :
Minimum Circuit Amperes (A)
TOCA :
Total Over Current Amperes (A)
MFA :
Maximum Fuse Amperes (A)
MSC :
Maximum Starting Current (A)
RLA :
Rated Load Amperes (A)
OFM :
Outdoor Fan Motor
kW :
Fan Motor rated output (kW)
FLA :
Full Load Amperes (A)
Содержание ARUN040GSS0
Страница 2: ...MULTI V S Outdoor Unit General information Product Data Installation of Outdoor Units Special Guide ...
Страница 3: ...General information MULTI V S Outdoor Unit 1 Model Line up External Appearance 2 Nomenclature ...
Страница 15: ...MULTI V S Outdoor Unit 3 Dimensions 10 Product Data ARUN100LSS0 ARUN120LSS0 Chassis U7 TBW35746501_Rev 01 ...
Страница 98: ...93 MULTI V S Outdoor Unit Product Data 10 Wiring Diagrams 10 1 4 HP U4 Chassis 1Ø ...
Страница 99: ...MULTI V S Outdoor Unit 10 Wiring Diagrams 94 Product Data 10 2 5 HP U4 Chassis 1Ø ...
Страница 100: ...10 Wiring Diagrams 95 MULTI V S Outdoor Unit Product Data 10 3 5 6 HP U3 Chassis 1Ø ...
Страница 101: ...MULTI V S Outdoor Unit 10 Wiring Diagrams 96 Product Data 10 4 4 5 6 HP 3Ø ...
Страница 102: ...10 Wiring Diagrams 97 MULTI V S Outdoor Unit Product Data 10 5 8 HP 3Ø ...
Страница 103: ...MULTI V S Outdoor Unit 10 Wiring Diagrams 98 Product Data 10 6 10 12 HP 3Ø ...
Страница 142: ...Special Guide MULTI V S Outdoor Unit 1 Caution for Refrigerant Leak 2 Installation Guide at the Seaside ...