Multi V S
Outdoor Unit
7. Refrigerant Piping System
16
Installation of Outdoor Units
■
Limits of pipe length and difference in height
Standard Model (ARUN****SS0)
Compact Model (ARUN****SL0)
Note
• * : Assume equivalent piping length of Y branch to be 0.5m, that of header to be 1m, calculation purpose.
• ** : To apply Conditional Application
WARNING
When the below condition is satisfied, the diameter of main pipe (A) must be increased accordingto below
table.
•
The equivalent length between outdoor unit and the farthest indoor unit is 90m or more
(Liquid and Gas pipes are increased)
* Compact models are not applied.
Connection method
Y branch only
Combination of
Y branch / header
Header only
Max. pipe length
Longest pipe length (L)
: between Outdoor Unit
↔
Indoor Unit
A+B+C+D+e
≤
150m(200m**)
A+B+b
≤
150m(200m**)
A+C+e
≤
150m(200m**)
A+f
≤
150 m
Longest pipe equivalent length* (L)
: between Outdoor Unit
↔
Indoor Unit
175m(225m**)
175m(225m**)
175m
Longest pipe length after 1st branch (
ℓ
)
40m (90 m**)
40m (90 m**)
40m
Total pipe length
300 m
300m
300m
Max. difference
in height
Difference in height (H)
: between Outdoor Unit
↔
Indoor Unit
50m
50m
50m
Difference in height (h)
: between Indoor Unit
↔
Indoor Unit
15m
15m
15m
Connection method
Y branch only
Combination of
Y branch / header
Header only
Max. pipe length
Longest pipe length (L)
: between Outdoor Unit
↔
Indoor Unit
A+B+C+D+e
≤
80m
A+B+b
≤
80 m
A+C+e
≤
80 m
A+f
≤
80 m
Longest pipe equivalent length* (L)
: between Outdoor Unit
↔
Indoor Unit
100 m
100 m
100 m
Longest pipe length after 1st branch (
ℓ
)
40 m
40 m
40 m
Total pipe length
150 m
150 m
150 m
Max. difference
in height
Difference in height (H)
: between Outdoor Unit
↔
Indoor Unit
30 m
30 m
30 m
Difference in height (h)
: between Indoor Unit
↔
Indoor Unit
15 m
15 m
15 m
Содержание ARUN040GSS0
Страница 2: ...MULTI V S Outdoor Unit General information Product Data Installation of Outdoor Units Special Guide ...
Страница 3: ...General information MULTI V S Outdoor Unit 1 Model Line up External Appearance 2 Nomenclature ...
Страница 15: ...MULTI V S Outdoor Unit 3 Dimensions 10 Product Data ARUN100LSS0 ARUN120LSS0 Chassis U7 TBW35746501_Rev 01 ...
Страница 98: ...93 MULTI V S Outdoor Unit Product Data 10 Wiring Diagrams 10 1 4 HP U4 Chassis 1Ø ...
Страница 99: ...MULTI V S Outdoor Unit 10 Wiring Diagrams 94 Product Data 10 2 5 HP U4 Chassis 1Ø ...
Страница 100: ...10 Wiring Diagrams 95 MULTI V S Outdoor Unit Product Data 10 3 5 6 HP U3 Chassis 1Ø ...
Страница 101: ...MULTI V S Outdoor Unit 10 Wiring Diagrams 96 Product Data 10 4 4 5 6 HP 3Ø ...
Страница 102: ...10 Wiring Diagrams 97 MULTI V S Outdoor Unit Product Data 10 5 8 HP 3Ø ...
Страница 103: ...MULTI V S Outdoor Unit 10 Wiring Diagrams 98 Product Data 10 6 10 12 HP 3Ø ...
Страница 142: ...Special Guide MULTI V S Outdoor Unit 1 Caution for Refrigerant Leak 2 Installation Guide at the Seaside ...