7. Refrigerant Piping System
15
Multi V S
Outdoor Unit
Installation of Outdoor Units
7.1.2 Compact Model (ARUN****SL0)
WARNING
•
Branch pipe can not be used after header.
•
Pipe length after header branching
–
It is recommended that difference in length of the pipes connected to the indoor units (a~f) is
minimized. Performance difference between indoor units may occur.
–
Indoor units should be installed at lower position than the header.
Y branch method
ⓐ
: Outdoor Unit
ⓑ
: 1st branch (Y branch)
ⓓ
: Indoor Units
Combination of Y branch / header method
ⓐ
: Outdoor Unit
ⓑ
: 1st branch (Y branch)
ⓒ
: Y branch
ⓓ
: Indoor Units
ⓔ
: Header
ⓕ
: Sealed piping
Header method
ⓐ
: Outdoor Unit
ⓓ
: Indoor Units
ⓔ
: Header
ⓕ
: Sealed piping
l 40m
h 15m
H 30m
L80m
Indoor
Unit
b
d
d
d
d
d
d
d
a
l 40m
h 15m
H 30m
L80m
b
c
d
d
d
d
d
e
f
a
l 40m
h 15m
H 30m
L80m
e
f
d
d
d
d
d
d
a
Содержание ARUN040GSS0
Страница 2: ...MULTI V S Outdoor Unit General information Product Data Installation of Outdoor Units Special Guide ...
Страница 3: ...General information MULTI V S Outdoor Unit 1 Model Line up External Appearance 2 Nomenclature ...
Страница 15: ...MULTI V S Outdoor Unit 3 Dimensions 10 Product Data ARUN100LSS0 ARUN120LSS0 Chassis U7 TBW35746501_Rev 01 ...
Страница 98: ...93 MULTI V S Outdoor Unit Product Data 10 Wiring Diagrams 10 1 4 HP U4 Chassis 1Ø ...
Страница 99: ...MULTI V S Outdoor Unit 10 Wiring Diagrams 94 Product Data 10 2 5 HP U4 Chassis 1Ø ...
Страница 100: ...10 Wiring Diagrams 95 MULTI V S Outdoor Unit Product Data 10 3 5 6 HP U3 Chassis 1Ø ...
Страница 101: ...MULTI V S Outdoor Unit 10 Wiring Diagrams 96 Product Data 10 4 4 5 6 HP 3Ø ...
Страница 102: ...10 Wiring Diagrams 97 MULTI V S Outdoor Unit Product Data 10 5 8 HP 3Ø ...
Страница 103: ...MULTI V S Outdoor Unit 10 Wiring Diagrams 98 Product Data 10 6 10 12 HP 3Ø ...
Страница 142: ...Special Guide MULTI V S Outdoor Unit 1 Caution for Refrigerant Leak 2 Installation Guide at the Seaside ...