Multi V S
Outdoor Unit
8. Electrical Wiring
24
Installation of Outdoor Units
• Types : 3-core cable
3.
Central control cable
4.
Separation of communication and power lines
• If communication and power lines are run alongside each other then there is a strong likelihood of operational
faults developing due to interference in the signal wiring caused by electrostatic and electromagnetic
coupling.
The tables below indicates our recommendation as to appropriate spacing of communication and powerlines
where these are to be run side by side
Note
• The figures are based on assumed length of parallel cabling up to 100m. For length in excess of 100m the figures
will have to be recalculated in direct proportion to the additional length of line involved.
• If the power supply waveform continues to exhibit some distortion the recommended spacing in the table should
be increased.
– If the cable are laid inside conduits then the following point must also be taken into account when grouping
various cable together for introduction into the conduits
– Power cable(including power supply to air conditioner) and communication cables must not be laid inside the
same
– In the same way, when grouping the power wires and communication cables should not be bunched together.
CAUTION
•
If apparatus is not properly earthed then there is always a risk of electric shocks, the earthing of the
apparatus must be carried out by a qualified person.
•
Use a power wire pipe for the power wiring.
Product type
Cable type
Diameter
ACP
2-core wire (shielding wire)
1.0~1.5mm²
AC Smart
2-core wire (shielding wire)
1.0~1.5mm²
AC Ez
4-core wire (shielding wire)
1.0~1.5mm²
Current capacity of power line
Spacing
100V or more
10A
300mm
50A
500mm
100A
1,000mm
Exceed 100A
1,500mm
Содержание ARUN040GSS0
Страница 2: ...MULTI V S Outdoor Unit General information Product Data Installation of Outdoor Units Special Guide ...
Страница 3: ...General information MULTI V S Outdoor Unit 1 Model Line up External Appearance 2 Nomenclature ...
Страница 15: ...MULTI V S Outdoor Unit 3 Dimensions 10 Product Data ARUN100LSS0 ARUN120LSS0 Chassis U7 TBW35746501_Rev 01 ...
Страница 98: ...93 MULTI V S Outdoor Unit Product Data 10 Wiring Diagrams 10 1 4 HP U4 Chassis 1Ø ...
Страница 99: ...MULTI V S Outdoor Unit 10 Wiring Diagrams 94 Product Data 10 2 5 HP U4 Chassis 1Ø ...
Страница 100: ...10 Wiring Diagrams 95 MULTI V S Outdoor Unit Product Data 10 3 5 6 HP U3 Chassis 1Ø ...
Страница 101: ...MULTI V S Outdoor Unit 10 Wiring Diagrams 96 Product Data 10 4 4 5 6 HP 3Ø ...
Страница 102: ...10 Wiring Diagrams 97 MULTI V S Outdoor Unit Product Data 10 5 8 HP 3Ø ...
Страница 103: ...MULTI V S Outdoor Unit 10 Wiring Diagrams 98 Product Data 10 6 10 12 HP 3Ø ...
Страница 142: ...Special Guide MULTI V S Outdoor Unit 1 Caution for Refrigerant Leak 2 Installation Guide at the Seaside ...