Installation Manual 57
ENGLISH
Electrical Wiring
Power supply switch
(Switch fuse : ELCB)
3 Phase 3 Wires Power line(R, S, T)
Communication line (3 line): Wired remote control
Single Phase of power supply line(L(1),L(2))
Communication line (2 shield line):
Between Outdoor Unit and Outdoor Unit
Power supply switch
(Switch)
Master
Slave1
Slave2
Communication line (2 shield line):
Between Indoor Unit and Outdoor Unit
■
When the power source is connected
In series between the units.
(Main Switch)
The GND terminal is a '–' terminal for the
central controller, not Ground Line
Between Indoor and Master Outdoor unit
Slave1
Outdoor unit
Master
Outdoor unit
Slave2
Outdoor unit
IDU
SODU
DRY1 DRY2 GND
INTERNET
B
A
12V
IDU
SODU
DRY1 DRY2 GND
INTERNET
B
A
12V
IDU
SODU
DRY1 DRY2 GND
INTERNET
B
A
12V
IDU
SODU
DRY1 DRY2 GND
INTERNET
B
B
B
B
B
A
A
A
A
A
12V
Master
Outdoor unit
3 Phase 3 Wires
Power supply
60Hz 208/230V
Power supply
1 Phase 60Hz
208/230V
Power supply switch
(Switch)
Power supply switch
(Switch fuse : ELCB)
3 Phase 3 Wires
Power supply
60Hz 208/230V
Power supply
1 Phase 60Hz
208/230V
■
When the power source is supplied to
Each outdoor unit individually.
(Main Switch)
Pull Box(Installer Option)
Pull Box(Installer Option)
■
3 Outdoor Units - 3Ø, 208/230V
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current
leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately
from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because
this system consists of the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power
goes on and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Содержание ARUB290DT2