Installation Manual 9
Installation Process
Outdoor units Information
CAUTION:
Ratio of the connectable Indoor Units to the Outdoor: Within 50 ~ 130%
Ratio of the running Indoor Units to the Outdoor: Within 10 ~ 100%
A combination operation over 100% cause to reduce the total capacity.
Power Supply: Outdoor Unit (3Ø, 460V, 60Hz)
■
Heat pump
Unit
System
HP
Ton
Model
Combination unit
Independent unit
Product Charge
kg(lbs)
CF(Correction Factor)
kg(lbs)
Max. Connectable No. of Indoor Units
Net Weight
kg
lbs
Dimensions
mm
(WxHxD)
inch
Connecting Pipes
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
1 Outdoor Unit
8
10
12
14
16
6.5
8.0
9.5
11.0
12.5
ARUN076DT2
ARUN096DT2 ARUN115DT2
ARUN134DT2 ARUN154DT2
8(17.6)
8(17.6)
8(17.6)
8(17.6)
8(17.6)
-1(-2.2)
0(0)
1(2.2)
2(4.4)
3(6.6)
13
16
19
23
26
240
285
285
285
285
529
628
628
628
628
1,280x1,607x730
1,280x1,607x730
1,280x1,607x730
1,280x1,607x730
1,280x1,607x730
(50-3/8 x 63-5/16 x 28-11/16) (50-3/8 x 63-5/16 x 28-11/16) (50-3/8 x 63-5/16 x 28-11/16) (50-3/8 x 63-5/16 x 28-11/16) (50-3/8 x 63-5/16 x 28-11/16)
9.52(3/8)
9.52(3/8)
12.7(1/2)
12.7(1/2)
12.7(1/2)
19.05(3/4)
22.2(7/8)
28.58(1 1/8)
28.58(1 1/8)
28.58(1 1/8)
Unit
System
HP
Ton
Model
Combination unit
Independent unit
Product Charge
kg(lbs)
CF(Correction Factor)
kg(lbs)
Max. Connectable No. of Indoor Units
Net Weight
kg
lbs
Dimensions
mm
(WxHxD)
inch
Connecting Pipes
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
2 Outdoor Units
18
20
22
24
14.5
16.0
17.5
19.0
ARUN173DT2
ARUN192DT2
ARUN211DT2
ARUN230DT2
ARUN096DT2
ARUN115DT2
ARUN134DT2
ARUN154DT2
ARUN076DT2
ARUN076DT2
ARUN076DT2
ARUN076DT2
8+8(17.6+17.6)
8+8(17.6+17.6)
8+8(17.6+17.6)
8+8(17.6+17.6)
-1(-2.2)
0(0)
1(2.2)
2(4.4)
29
32
35
39
285+240
285+240
285+240
285+240
628+529
628+529
628+529
628+529
(1,280x1,607x730)x2
(1,280x1,607x730)x2
(1,280x1,607x730)x2
(1,280x1,607x730)x2
((50-3/8 x 63-5/16 x 28-11/16) x 2) ((50-3/8 x 63-5/16 x 28-11/16) x 2)
((50-3/8 x 63-5/16 x 28-11/16) x 2) ((50-3/8 x 63-5/16 x 28-11/16) x 2)
15.88(5/8)
15.88(5/8)
15.88(5/8)
15.88(5/8)
28.58(1 1/8)
28.58(1 1/8)
28.58(1 1/8)
34.9(1 3/8)
Unit
System
HP
Ton
Model
Combination unit
Independent unit
Product Charge
kg(lbs)
CF(Correction Factor)
kg(lbs)
Max. Connectable No. of Indoor Units
Net Weight
kg
lbs
Dimensions
mm
(WxHxD)
inch
Connecting Pipes
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
2 Outdoor Units
26
28
30
32
20.5
22.5
24.0
25.5
ARUN250DT2
ARUN270DT2
ARUN290DT2
ARUN310DT2
ARUN134DT2
ARUN134DT2
ARUN154DT2
ARUN154DT2
ARUN115DT2
ARUN134DT2
ARUN134DT2
ARUN154DT2
8+8(17.6+17.6)
8+8(17.6+17.6)
8+8(17.6+17.6)
8+8(17.6+17.6)
3(6.6)
4(8.8)
5(11.0)
6(13.2)
42
45
49
52
285x2
285x2
285x2
285x2
628x2
628x2
628x2
628x2
(1,280x1,607x730)x2 (1,280x1,607x730)x2
(1,280x1,607x730)x2 (1,280x1,607x730)x2
((50-3/8 x 63-5/16 x 28-11/16) x 2) ((50-3/8 x 63-5/16 x 28-11/16) x 2)
((50-3/8 x 63-5/16 x 28-11/16) x 2) ((50-3/8 x 63-5/16 x 28-11/16) x 2)
19.05(3/4)
19.05(3/4)
19.05(3/4)
19.05(3/4)
34.9(1 3/8)
34.9(1 3/8)
34.9(1 3/8)
34.9(1 3/8)
Содержание ARUB290DT2