Installation Manual 11
Outdoor Units Information
ENGLISH
Unit
System
HP
Ton
Model
Combination unit
Independent unit
Product Charge
kg(lbs)
CF(Correction Factor)
kg(lbs)
Max. Connectable No. of Indoor Units
Net Weight
kg
lbs
Dimensions
mm
(WxHxD)
inch
Connecting Pipes
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
2 Outdoor Unit
18
20
22
24
14.5
16.0
17.5
19.0
ARUN173BT2
ARUN192BT2
ARUN211BT2
ARUN230BT2
ARUN096BT2
ARUN096BT2
ARUN115BT2
ARUN115BT2
ARUN076BT2
ARUN096BT2
ARUN096BT2
ARUN115BT2
8+8(17.6+17.6)
8+8(17.6+17.6)
8+8(17.6+17.6)
8+8(17.6+17.6)
-1(-2.2)
0(0)
1(2.2)
2(4.4)
29
32
35
39
285+285
285+285
285+285
285+285
628+628
628+628
628+628
628+628
(1,280x1,607x730)x2 (1,280x1,607x730)x2
(1,280x1,607x730)x2 (1,280x1,607x730)x2
((50-3/8 x 63-5/16 x 28-11/16) x 2)
((50-3/8 x 63-5/16 x 28-11/16) x 2)
((50-3/8 x 63-5/16 x 28-11/16) x 2)
((50-3/8 x 63-5/16 x 28-11/16) x 2)
15.88(5/8)
15.88(5/8)
15.88(5/8)
15.88(5/8)
28.58(1 1/8)
28.58(1 1/8)
28.58(1 1/8)
34.9(1 3/8)
Unit
System
HP
Ton
Model
Combination unit
Independent unit
Product Charge
kg(lbs)
CF(Correction Factor)
kg(lbs)
Max. Connectable No. of Indoor Units
Net Weight
kg
lbs
Dimensions
mm
(WxHxD)
inch
Connecting Pipes
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
3 Outdoor Unit
26
28
30
32
20.5 22.5 24.0 25.5
ARUN250BT2
ARUN270BT2
ARUB290DT2
ARUB310DT2
ARUN096BT2
ARUN096BT2
ARUN096BT2
ARUN115BT2
ARUN076BT2
ARUN096BT2
ARUN096BT2
ARUN096BT2
ARUN076BT2
ARUN076BT2
ARUN096BT2
ARUN096BT2
8+8+8(17.6+17.6+17.6)
8+8+8(17.6+17.6+17.6)
8+8+8(17.6+17.6+17.6) 8+8+8(17.6+17.6+17.6)
-2(-4.4)
-1(-2.2)
0(0)
1(2.2)
42
45
49
52
285+285+285
285+285+285
285+285+285
285+285+285
628+628+628
628+628+628
628+628+628
628+628+628
(1280x1607x730)x3
(1280x1607x730)x3
(1280x1607x730)x2
(1280x1607x730)x2
(50.4x63.3x28.7)x3 (50.4x63.3x28.7)x3 (50.4x63.3x28.7)x2 (50.4x63.3x28.7)x2
19.05(3/4)
19.05(3/4)
19.05(3/4)
19.05(3/4)
34.9(1 3/8)
34.9(1 3/8)
34.9(1 3/8)
34.9(1 3/8)
Unit
System
HP
Ton
Model
Combination unit
Independent unit
Product Charge
kg(lbs)
CF(Correction Factor)
kg(lbs)
Max. Connectable No. of Indoor Units
Net Weight
kg
lbs
Dimensions
mm
(WxHxD)
inch
Connecting Pipes
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
3 Outdoor Unit
34
36
27.0 28.5
ARUN330DT2
ARUN350DT2
ARUN115BT2
ARUN115BT2
ARUN115BT2
ARUN115BT2
ARUN096BT2
ARUN115BT2
8+8+8(17.6+17.6+17.6)
8+8+8(17.6+17.6+17.6)
2(4.4)
3(6.6)
55
58
285+285+285
285+285+285
628+628+628
628+628+628
(1280x1607x730)x2
(1280x1607x730)x2
(50.4x63.3x28.7)x2
(50.4x63.3x28.7)x2
19.05(3/4)
19.05(3/4)
34.9(1 3/8)
41.3(1 5/8)
Содержание ARUB290DT2