15
General Installation Guidelines
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
GENERAL INSTALLATION GUIDELINES
Figure 4: Single Fan Outdoor Unit Service Access and Allowable Clearances Diagram.
Unit: Inch
A
B
C
D
E
F
G
Case 1
Standard
12
24
-
12
-
-
-
Minimum
4
10
-
4
-
-
40
Case 2
Standard
-
-
20
-
-
-
-
Minimum
-
-
14
-
-
-
40
Case 3
Standard
-
-
20
12
-
-
-
Minimum
-
-
14
4
-
-
-
Case 4
Standard
-
-
-
12
24
-
-
Minimum
-
-
-
4
8
79
-
Case 5
Standard
-
24
-
12
-
-
-
Minimum
-
10
-
4
-
-
-
Table 4: Single Fan Outdoor Unit Service Access and Allowable Clearances Diagram Legend.
Do not place the unit where animals
and/or plants will be in the path of the warm
air, or where the warm air and/or noise will
disturb neighbors.
If the outdoor unit is installed between standard and minimum clearances, capacity decreases approximately 10%.
Minimum Clearance Requirements for Single Fan Outdoor Units
Proper clearance for the outdoor unit coil is critical for proper operation. When installing the outdoor unit, consider service, inlet and outlet,
and minimum allowable space requirements as illustrated in the diagrams below.
Specific clearance requirements in the diagram below are for single fan outdoor units. Figure below shows the overall minimum clearances
that must be observed for safe operation and adequate airflow around the outdoor unit.
When placing the outdoor unit under an overhang, awning, sunroof or other “roof-like structure”, observe the clearance requirements (as
shown in Cases 1 and 2) for height in relation to the unit. This clearance ensures that heat radiation from the condenser is not restricted
around the unit.
Adhere to all clearance requirements if installing the unit on a roof. Be sure to level the unit and ensure that the unit is adequately anchored.
Consult local codes for rooftop mounting requirements. To have successful service access to the outdoor unit, see figure below for minimum
spacing. When installing multiple outdoor units, see Cases 4 and 5 in the figure below for correct spacing requirements. Outdoor unit fans
draw air from the back of the unit and discharge out the front. Place units back to back and front to front.
A
B
D
G
C
G
C
D
E
D
D
B
B
F
1/16 inch
20 inches or less
Case 1
Case 4
Case 2
Case 3
Case 5
20 inches or less
Required Outdoor Unit Clearances