GENERAL INSTALLATION GUIDELINES
Maintenance Clearances
Chassis Code
Control Panel Access
Major Maintenance Access
Location
C1
C2
C3
Location
A1
A2
A3*
High-Static Ducted Indoor Units
M1
Right End
8
8
10
Bottom
40
32
12
M2
Right End
8
8
10
Bottom
50
28
12
M3
Right End
8
8
12
Bottom
50
28
15
B8
Right End
12
14
18
Bottom
62
28
19
Low-Static Ducted Indoor Units
L1
Right End
10
12
8
Bottom
30
25
8
L2
Right End
10
12
8
Bottom
38
25
8
L3
Right End
10
12
8
Bottom
46
25
8
Table 15: Minimum Maintenance Clearances (in.).
C2
C1
C3
A3
A1
A2
Figure 15: High-Static Ducted (B8) Indoor Unit
Maintenance Clearances.
Figure 16: Low-Static Ducted (L1/L2/L3) Indoor Unit
Maintenance Clearances.
Figure 17: High-Static Ducted (M1/M2/M3) Indoor Unit
Maintenance Clearances.
*Does not apply when the ceiling surface below can be removed.
A1
A2
A3
C2 C1
C3
A1
A2
A3
C2
C1
C3
Figure 18: High-Static Ducted (B8/M1/M2/M3) Indoor Unit
Maintenance Clearances.
[Unit: inch]
Top view
Front
Inspection hole
23-5/8 x 23-5/8
Control box
39-3/8
Air outlet
vents
Air inlet vents
23-5/8
10