GENERAL DATA
Electrical
−
High-Static M1/M2/M3/B8 Chassis
Table 10: Ducted High Static Indoor Unit Electrical Data.
Model
Voltage Range
MCA
MOP
Rated
Amps
(A)
Power Supply
Power Input (W)
Hz
Volts
Phase Max.Cooling Max.Heating
L / M / H at
Factory Default
M1 Units
ARNU073M1A4
208-230
2.0
15
1.6
60 208-230
1
190
190
25 / 30 / 39
ARNU093M1A4
2.0
1.6
190
190
26 / 32 / 40
ARNU123M1A4
2.0
1.6
190
190
31 / 38 / 46
ARNU153M1A4
2.0
1.6
190
190
46 / 53 / 67
ARNU183M1A4
2.0
1.6
190
190
55 / 63 / 85
ARNU243M1A4
2.0
1.6
190
190
58 / 74 / 91
M2 Units
ARNU073M2A4
208-230
2.9
15
2.3
60 208-230
1
430
430
21 / 29 / 38
ARNU093M2A4
2.9
2.3
430
430
21 / 29 / 38
ARNU123M2A4
2.9
2.3
430
430
25 / 34 / 43
ARNU153M2A4
2.9
2.3
430
430
25 / 34 / 43
ARNU183M2A4
2.9
2.3
430
430
34 / 43 / 67
ARNU243M2A4
2.9
2.3
430
430
34 / 43 / 67
ARNU283M2A4
2.9
2.3
430
430
57 / 88 / 123
ARNU363M2A4
2.9
2.3
430
430
88 / 123 / 184
ARNU423M2A4
2.9
2.3
430
430
136 / 193 / 231
M3 Units
ARNU283M3A4
208-230
3.1
15
2.5
60 208-230
1
650
650
60 / 83 / 109
ARNU363M3A4
3.1
2.5
650
650
75 / 107 / 161
ARNU423M3A4
3.1
2.5
650
650
75 / 107 / 161
ARNU483M3A4
3.1
2.5
650
650
75 / 107 / 172
ARNU543M3A4
3.1
2.5
650
650
172 / 215 / 260
B8 Units
ARNU363B8A4
208-230
6.5
15
5.2
60 208-230
1
800
800
403 / 420 / 478
ARNU423B8A4
6.5
5.2
800
800
465 / 497 / 528
ARNU483B8A4
6.5
5.2
800
800
482 / 500 / 538
ARNU763B8A4
6.5
5.2
800
800
505 / 505 / 765
ARNU963B8A4
6.5
5.2
800
800
750 / 750 / 800
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use the circuit breaker.
Max. power input is rated at maximum setting value.