Specifications
−
Vertical Air Handler NJ Chassis
Table 8: Vertical / Horizontal NJ Chassis Air Handler Unit General Data.
Model No.
ARNU123NJA4
ARNU183NJA4
ARNU243NJA4
ARNU303NJA4
ARNU363NJA4
Cooling Mode Performance
Capacity (Btu/h)
12,000
18,000
24,000
30,000
36,000
Max Power Input
1
(W)
228
228
228
228
228
L/M/H Power Input at Factory Default (W)
47 / 64 / 80
64 / 80 / 90
64 / 96 / 120
94 / 133 / 180
133 / 180 / 230
Heating Mode Performance
Capacity (Btu/h)
13,500
20,000
27,000
34,000
40,000
Max Power Input
1
(W)
228
228
228
228
228
L/M/H Power Input at Factory Default (W)
47 / 64 / 80
64 / 80 / 90
64 / 96 / 120
94 / 133 / 180
133 / 180 / 230
Entering Mixed Air
Cooling Max. (°F WB)
76
76
76
76
76
Heating Min. (°F DB)
2
59
59
59
59
59
Unit Data
Refrigerant Type
3
R410A
R410A
R410A
R410A
R410A
Refrigerant Control
EEV
EEV
EEV
EEV
EEV
Sound Pressure
4
dB(A) (H/M/L)
42 / 41 / 39
42 / 42 / 41
43 / 42 / 41
44 / 43 / 42
45 / 44 / 43
Net Unit Weight (lbs.)
117
117
117
117
121
Shipping Weight (lbs.)
140
140
140
140
144
Communication Cable
5
(No. x AWG)
2 x 18
2 x 18
2 x 18
2 x 18
2 x 18
Fan
Type
Sirocco
Sirocco
Sirocco
Sirocco
Sirocco
Motor
1
1
1
1
1
Housing
1
1
1
1
1
Motor/Drive
Brushless Digitally Controlled / Direct
Airflow Rate H/M/L (CFM) Standard Mode
530 / 480 / 380
580 / 530 / 480
710 / 640 / 480
880 / 800 / 630
990 / 880 / 800
Airflow Rate H/M/L (CFM) High Mode
(Factory Set)
530 / 480 / 380
580 / 530 / 480
710 / 640 / 480
880 / 800 / 630
990 / 880 / 800
External Static Pressure (in. wg)
Standard Mode
0.3
0.3
0.3
0.3
0.3
External Static Pressure (in. wg)
High Mode (Factory Set)
0.5
0.5
0.5
0.5
0.5
Piping
Liquid Line (in., O.D.)
1/4 Brazed
1/4 Brazed
3/8 Brazed
3/8 Brazed
3/8 Brazed
Vapor Line (in., O.D.)
1/2 Brazed
1/2 Brazed
5/8 Brazed
5/8 Brazed
5/8 Brazed
Condensate Line (in., I.D.)
1
1
1
1
1
EEV: Electronic Expansion Valve
Power wiring is field supplied and must comply with the applicable local and national
codes.
This unit comes with a dry nitrogen charge.
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change
without notice. Current certified ratings are available at www.ahridirectory.org.
1
Max power input is rated at maximum setting value.
2
Low ambient performance with LGRED° heat technology is included in Multi V 5 Air
Source Units produced after February 2019.
3
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA.
4
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5
All communication cable to be minimum 18 AWG, 2-conductor, twisted, stranded, shielded
and must comply with applicable local and national codes. Shield must be joined and
insulated throughout. Ensure the communication cable is properly grounded at the master
outdoor unit only. Do not ground the ODU-IDU communication cable at any other point.