Service Manual
181
Troubleshooting Guide
Outdoor 4way
(reversing valve)
Switching Error
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
151
When the Main or the Sub
outdoor has one of them
having a 4way valve error
Concerned
Remote
Controller
Outdoor unit
1. 4 way valve error due to the inlet of
sludge into the valve
2. Comp damage leading to pressure
change does not occur ,
3. Wrong installation of common pipe
between the outdoor units
4. 4way valve error
■
Defect inspection method
1) Check whether the piping between the outdoor units is normal
(liquid pipe should be connected to liquid pipe, common pipe be connected to common pipe ) fi Pipe modifica-
tion
2) Check whether the Main/Sub outdoor compressor is damaged or not.(Refer to CH21)
3) Please confirm the Main PCB's 4way valve terminal voltage (220V±10%).
In case of abnormal voltage please replace the outdoor main PCB
4) Check the outdoor PCB's 4way valve connector connections and coil connections.
5) Measure the 4way valve's coil resistance at the connector
Normal resistance :
6) In case the error still persists even after the all above conditions are normal then replace the 4way valve .
Содержание ARNU Series
Страница 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Страница 16: ...16 ...
Страница 17: ...Service Manual 17 Indoor Units ...
Страница 18: ...18 Indoor Unit ...
Страница 30: ...30 Indoor Unit ...
Страница 44: ...44 Indoor Unit ...
Страница 79: ...Service Manual 79 Outdoor unit ...
Страница 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Страница 112: ...112 Outdoor Unit ...
Страница 113: ...Service Manual 113 Trouble shooting guide ...
Страница 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Страница 140: ...Troubleshooting Guide 140 Outdoor Unit Check 3 phase rectification diode Measure input power between phases R S R T S T ...
Страница 141: ...Service Manual 141 Troubleshooting Guide Measure input power of one phase R S T Connector of compressor ...
Страница 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Страница 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Страница 144: ...Troubleshooting Guide 144 Outdoor Unit Measure current of IPM U V W Measure voltage of IPM P N ...
Страница 149: ...Service Manual 149 Troubleshooting Guide SVC valve Measure resistance on the pressure switch connector ...
Страница 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Страница 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Страница 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Страница 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Страница 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Страница 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Страница 164: ...Troubleshooting Guide 164 Outdoor Unit Pressure sensor connector High pressure sensor Low pressure sensor ...
Страница 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Страница 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Страница 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Страница 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Страница 182: ...Troubleshooting Guide 182 Outdoor Unit 4way valve in the outdoor unit 4way valve connector on the Main PCB ...
Страница 183: ...Service Manual 183 Exploded View Replacement Parts List ...