Troubleshooting Guide
136
Outdoor Unit
Protection of
Inverter compres-
sor from over cur-
rent (Detection of
over 80A per
1.8ms IPM )
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
21
Defective inverter com-
pressor, Inverter element
(IPM) defect
Concerned
Remote controller
Panel Display
Outdoor unit
1. Over current detection at the invert-
er compressor (U,V,W)
2. IPM Overheating .
3. Insulation damage of the compres-
sor / motor damage
5. Low input voltage at the outdoor
6. Inverter compressor terminal dis-
connected or loose .
7. Inverter PCB/IPM PCB defect
■
Defect inspection method :
1) Check whether the insulation of the compressor, motor coil resistance is normal ? Otherwise, replace the com-
pressor .
- Motor Coil resistance normalcy : Resistance between each terminal of Inverter compressor =1.33
Ω
±7% ,
Resistance between the each terminal of the constant speed compressor =1.83
Ω
±7% (The 3 measured value
must be similar)
- Insulation normalcy : Resistance between the compressor terminal and the product body = Above 2M
Ω
(Measured within specified time after the compressor stop )
2) Check whether the IPM/3 phase rectification Diode is normal ? Otherwise, replace the IPM/ Diode .
- Tester : After setting the Diode mode , test with the tester probe in + ,- sequence.
- IPM:'U-P/V-P/W-P' measurement : 0.3~0.6 V, Reverse polarity measurement :Above 2.6 V
'N-U/N-V/N-W' measurement : 0.3~0.6 V, Reverse polarity measurement : Above 2.6 V
- 3 phase rectification diode : ~ & + / ~ & + / ~ & +' sequential measurement : 0.3~0.6 V,
Reverse polarity measurement : Above 2.6V
3) Check whether the input voltage is 360V~410V(AC).
4) Check the balance between each phase at the main breaker of the building (phase distribution ) (Below 5~10V).
5) Check whether the terminal connection is normal ?
(Comp connecting terminal, IPM connecting terminal, diode connecting terminal, capacitor connecting terminal)
6) Check whether the IPM Pin connecting to PCB soldering is normal ?
(Dismantle the PCB and check the soldering at the back side of the PCB .)
In case if any abnormality please replace the IPM PCB.
7) Check whether the Outdoor Unit fan is working ? In case of any abnormality please check the outdoor fan
(Refer to CH105~CH108)
8) Check whether the supplied power is normal or insufficient.
9) After the inspection, check whether the input power to the IPM during the trial run is 450V~560V(DC).
(Set the tester at the DC mode)
Check the IPM terminal connecting condition.
(Comp connecting terminal, IPM connecting terminal, diode connecting terminal, capacitor connecting terminal )
10) Measure the current at each phase (U,V,W) of the inverter compressor during the trial run after the completion
of the inspection.
In case the deviation between the current in each phase is above 1.5A then replace the PCB .
Содержание ARNU Series
Страница 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Страница 16: ...16 ...
Страница 17: ...Service Manual 17 Indoor Units ...
Страница 18: ...18 Indoor Unit ...
Страница 30: ...30 Indoor Unit ...
Страница 44: ...44 Indoor Unit ...
Страница 79: ...Service Manual 79 Outdoor unit ...
Страница 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Страница 112: ...112 Outdoor Unit ...
Страница 113: ...Service Manual 113 Trouble shooting guide ...
Страница 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Страница 140: ...Troubleshooting Guide 140 Outdoor Unit Check 3 phase rectification diode Measure input power between phases R S R T S T ...
Страница 141: ...Service Manual 141 Troubleshooting Guide Measure input power of one phase R S T Connector of compressor ...
Страница 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Страница 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Страница 144: ...Troubleshooting Guide 144 Outdoor Unit Measure current of IPM U V W Measure voltage of IPM P N ...
Страница 149: ...Service Manual 149 Troubleshooting Guide SVC valve Measure resistance on the pressure switch connector ...
Страница 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Страница 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Страница 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Страница 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Страница 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Страница 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Страница 164: ...Troubleshooting Guide 164 Outdoor Unit Pressure sensor connector High pressure sensor Low pressure sensor ...
Страница 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Страница 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Страница 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Страница 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Страница 182: ...Troubleshooting Guide 182 Outdoor Unit 4way valve in the outdoor unit 4way valve connector on the Main PCB ...
Страница 183: ...Service Manual 183 Exploded View Replacement Parts List ...