Troubleshooting Guide
130
Indoor Unit
[In case only one Indoor Unit or only few Indoor Units display 'ch05' error ]
1) Re-operate the Auto-Addressing function and then confirm the Auto-Addressing in all Indoor Units.
Auto-Addressing can be confirmed at the Wired Remote Controller.
In case of the Indoor Units not having the Wired Remote Controller, check the blinking counts of the Indoor
Unit panel (Auto-Addressing must be operated after minimum 1 minute of power On ) › Check the Indoor Unit
not having Auto-Addressing and replace the concerned unit PCB if required.
2) Make sure to separate the communication wire and the power line (AC220/380V ) by a distance of minimum
30 cm.
CAUTION
• In case you replace the communication wire by power 220V line, then the connected PCB gets damaged
or burnt.
To carry out Auto-Addressing
function, press red button until
you see '88 'displayed on 88
segment as shown in left
side picture.
7
segment
Содержание ARNU Series
Страница 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Страница 16: ...16 ...
Страница 17: ...Service Manual 17 Indoor Units ...
Страница 18: ...18 Indoor Unit ...
Страница 30: ...30 Indoor Unit ...
Страница 44: ...44 Indoor Unit ...
Страница 79: ...Service Manual 79 Outdoor unit ...
Страница 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Страница 112: ...112 Outdoor Unit ...
Страница 113: ...Service Manual 113 Trouble shooting guide ...
Страница 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Страница 140: ...Troubleshooting Guide 140 Outdoor Unit Check 3 phase rectification diode Measure input power between phases R S R T S T ...
Страница 141: ...Service Manual 141 Troubleshooting Guide Measure input power of one phase R S T Connector of compressor ...
Страница 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Страница 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Страница 144: ...Troubleshooting Guide 144 Outdoor Unit Measure current of IPM U V W Measure voltage of IPM P N ...
Страница 149: ...Service Manual 149 Troubleshooting Guide SVC valve Measure resistance on the pressure switch connector ...
Страница 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Страница 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Страница 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Страница 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Страница 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Страница 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Страница 164: ...Troubleshooting Guide 164 Outdoor Unit Pressure sensor connector High pressure sensor Low pressure sensor ...
Страница 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Страница 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Страница 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Страница 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Страница 182: ...Troubleshooting Guide 182 Outdoor Unit 4way valve in the outdoor unit 4way valve connector on the Main PCB ...
Страница 183: ...Service Manual 183 Exploded View Replacement Parts List ...