CO
2
INTERLOCK
ADVANCED
The CO
2
Interlock menu allows the user to enable the CO
2
interlock mode and adjust
control parameters which related with Fan operation
CO
2
INTERLOCK ENABLE
This screen allows the user to Enable the CO
2
Interlock function
CO
2
INTERLOCK SETTINGS
This screen allows the user to adjust CO
2
interlock mode control parameter
- Setpoint: Target Space CO
2
(ppm)
- Stop Setpoint: Fan stop when Space CO
2
value is below Stop Setpoint
- Hysteresis: The fan speed is adjusted by reflecting the hysteresis in the target
value
The Advanced menu allows the user to access several submenus regarding
controller information, and unit configuration. Submenu options are read only and will
require the user to input proper login criteria. The service password (7600) is
required to change service access menus. Consult factory for factory level access.
The Unit Configuration Settings Menus allows the user to view and adjust Altitude
and functions
ALTITUDE
This screen allow to adjust the Altitude. The unit altitude is used for the enthalpy
calculation.
FUNTIONS SETTINGS
This screen allow to set functions.
-. Power Loss Auto Reset:
-. Shut Down Alarm Auto Reset:
-. Forced Operation
:
21