Test Run Control (
①
)
Test Run
– Activates “Test Run” mode.
Remain Time
– Display the remaining “Test Run”
time.
Test Phase
– Display the ongoing test status
Rooftop DOAS:
[
"Test Ready" > "OA Damper Testing" > "EA
Damper Testing" > "Recirc. Damper Testing" > "SA
Fan Testing" > "EA Fan Testing" > "ERW Testing" >
"Main Coil #1 Testing" > "Main Coil #2 Testing"
>"Reheat Coil Testing" > "Recovery Coil Testing",
"Test Done"]
Compact DOAS:
["Test Ready" > "SA Fan Testing" > "Main Coil
Testing" > "Reheat Coil Testing" > "Test Done"]
Test Mode
– Display the test mode.
Operation mode will be define with OA
condition and Unit setting
Test Result (
②
)
When the test is in progress, the test result of each
items is displayed.
Waiting
– Item is not tested.
Testing
– Item is testing.
OK
– Item test result is ok.
Fail
– Item test result is failed.
Unit Overview (
③
)
Display the monitoring points of the unit
Chart (
④
)
Display the monitoring points of the unit as a chart.
Saving Trend (
⑤
)
When click the download button on the right side of the
screen, the “Save Variable Trend” screen pops up, and
by setting the file name in the popped up screen, the
current values of the control points of the Test Run
screen are saved in the CSV file.
SVC > Test Run
The service manager can test run the unit and check the key points associated with
the unit controller.
42