background image

- 2 -

Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes

LGE Internal Use Only

1. Specification

Notes:-

1. Capacities are based on the following conditions:

Cooling  • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB

• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting piping length 7.5m
• Level difference of zero

Heating

• Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting piping length 7.5m
•  Level difference of zero

2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available models
5. EEV : Electronic expansion valve

Conversion formula

kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m

3

/min x 35.3

l/s = CMM x 1000/60 

Indoor unit type

1Way ceiling cassette (art type)

Model

AMNW09GTUC0

[MT09AH NU1]

AMNW12GTUC0

[MT12AH NU1]

Power Supply

Ø / V / Hz

1/220~240/50

1/220~240/50

Cooling Capacity

kW

2.64

3.52

Btu/h

9,000

12,000

Heating Capacity

kW

2.93

3.87

Btu/h

10,000

13,200

Current

Nominal Running Current 

A

0.2

0.2

Fan

Motor Type

BLDC

BLDC

Fan Type

Cross Flow Fan

Cross Flow Fan

Motor Output(W) x No. of Unit

20 x 1

20 x 1

Air Flow Rate
(H / M / L)

CMM

7.5/7.3/6.8

8.1/7.4/7.0

CFM

265/258/240

286/261/247

Capacitor

μ

F / Vac

-

-

Drive

Direct Drive

Direct Drive

Coil

Row x Column x FPI

2R x 12C x 18

2R x 12C x 18

Dimensions (W x H x D)

Body

mm

860 x 132 x 450

860 x 132 x 450

inch

33.8 x 5.2 x 17.7

33.8 x 5.2 x 17.7

Front Panel

mm

1,100 x 34 x 500

1,100 x 34 x 500

inch

43.3 x 1.3 x 19.7

43.3 x 1.3 x 19.7

Net Weight

Body

kg (lbs)

13.5(29.8)

13.5(29.8)

Package

kg (lbs)

17.0(37.5)

17.0(37.5)

Sound Level (H / M / L)

dB(A) + 3

36/34/32

37/36/33

Piping
Connections

Liquid

mm(inch)

6.35(1/4)

6.35(1/4)

Gas

mm(inch)

9.52(3/8)

9.52(3/8)

Drain(OD/ID)

mm

Φ32.0 / 25.0

Φ32.0 / 25.0

Safety Devices

Fuse, Thermal Protector for Fan Motor

Temperature Sensor

Thermistor

Thermistor

Referigerant

R410A

R410A

Referigerant Control

EEV(in Outdoor unit or BD) EEV(in Outdoor unit or BD)

Connectable Outdoor Unit

Multi F / FDX series

Multi F / FDX series

Power and Transmission Interunit Cable

No. x mm

2

4 x 0.75(including earth)

4 x 0.75(including earth)

Содержание AMNH09GTUC0

Страница 1: ...er SVC MANUAL Exploded View MODEL AMNH09GTUC0 AMNH12GTUC0 CAUTION Before Servicing the unit read the safety precautions in General SVC manual Only for authorized service personnel Internal Use Only http biz lgservice com ...

Страница 2: ...12 000 Heating Capacity kW 2 93 3 87 Btu h 10 000 13 200 Current Nominal Running Current A 0 2 0 2 Fan Motor Type BLDC BLDC Fan Type Cross Flow Fan Cross Flow Fan Motor Output W x No of Unit 20 x 1 20 x 1 Air Flow Rate H M L CMM 7 5 7 3 6 8 8 1 7 4 7 0 CFM 265 258 240 286 261 247 Capacitor μF Vac Drive Direct Drive Direct Drive Coil Row x Column x FPI 2R x 12C x 18 2R x 12C x 18 Dimensions W x H x...

Страница 3: ...ungus Installation Drain pump E S P control Electric heater operation X High ceiling operation Reliability Hot start Self diagnosis Soft dry operation Convenience Auto changeover X Auto cleaning Auto operation artificial intelligence Auto restart operation Child lock Forced operation Group control Sleep mode Timer on off Timer weekly Two thermistor control Individual control Standard wired remote ...

Страница 4: ... Use Only 3 Piping Diagrams Heat exchanger C F F lndoor unit Th3 Th2 Th1 Heating Cooling M Refrigerant pipe connection port diameter Model AMNH09GTUC0 AMNH12GTUC0 Gas Ø9 52 3 8 Ø9 52 3 8 Liquid Ø6 35 1 4 Ø6 35 1 4 Unit mm inch LOC Description Th1 Room thermistor Th2 Pipe in thermistor Th3 Pipe out thermistor ...

Страница 5: ...Dip switch setting Off On Remarks SW3 Group Master Slave Group control setting using wired remote controller Dry contact mode setting 1 Variable Auto manual mode can be chosen by wide wired SW4 Dry contact Variable Auto remote controller or wireless remote controller when shipped from factory manual mode 2 Auto For dry contact it is always auto mode 1 Duct model Off Default not operate continuosly...

Страница 6: ...66010 552111 354210 263230B 359011 352380D 135500A 346810 352380A 135500C 352150 135511 131410 352150 266090 135500B 267110 149304 342800 158580 159830B 152500 268711B 249940 263230A 135500D W6640 249951 268711D Model AMNH GTUC0 Location No Description Sensor Information Housing color 263230A Thermistor 1 Air Yellow 263230B Thermistor 2 Pipe in White 263230C Thermistor 3 Pipe Out Red ...

Страница 7: ...Only for training and service purposes LGE Internal Use Only 5 Exploded View W4810B 147740 146811 145200D 145200B 145200C 147582 147581 W4810A 137213A 135800 135316 137211 137213B W4810A 145200A 135500 146811 268711 TU chassis Front panel grille type PT UUC1 ...

Страница 8: ...P NO MFL67568601 MAY 2012 ...