- 5 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
4. Wiring Diagrams
CN-MOTOR1 CN-FLOAT
CN-DISPLAY
CN-D/PUMP CN-VANE1
CN-POWER
CN-REMO
CN-PIPE/OUT
CN-PIPE/IN
CN-ROOM
CN-AIRC
CAUTION
For Multi model, dip switch 1,2,6,7,8 must be set off.
Those dip switches are used for other models.
Dip switch setting
Off
On
Remarks
SW3
Group
Master
Slave
Group control setting using wired remote controller
Dry contact mode setting
1. Variable : Auto/manual mode can be chosen by wide wired
SW4
Dry contact
Variable
Auto
remote controller or wireless remote controller
(when shipped from factory
→
manual mode)
2. Auto : For dry contact, it is always auto mode.
1. Duct model
-. Off : Default(not operate continuosly )
-. On : Fan operate continuosly
SW5
Extra 1
Off
On
2. Cassette model : No function
3. Ceiling suspended model
-. Off : Ceiling(default)
-. On : Floor
Model: AMNH**GTUC0