Features

INTRODUCTION

Air Intake Vents

Connecting
Wires

Piping

Air Outlet Vents

Base Plate

Drain Hose

Front grille 

Air filter 

On/Off button

Signal receiver 
Display

Plasmaster Ionizer

Air deflector

(Vertical louver & Horizontal vane)

Air outlet 

* The feature can be changed according to type of model.

NOTE

• When mechanical connectors are reused indoors, sealing parts shall be renewed. 

INSTALLATION MAP

Connecting cable
(Optional Parts) 

Vinyl tape (Wide)

• Apply after carrying out a
  drainage test.
• To carry out the drainage 
  test, remove the air filters
  and pour water into the heat 
  exchanger.

Saddle

Gas side piping       (Optional Parts)

Liquid side piping       (Optional Parts)

Additional drain pipe

Vinyl tape (Narrow)
Drain hose

Installation plate
Sleeve
Bushing-Sleeve
Putty(Gum Type Sealant)

Bend the pipe as closely 
on the wall as possible, 
but be careful that it 
doesn't break.

• You should purchase the installation parts. (lt can be changed according to market) 

• Pipes and wires should be purchased separately for installation of the product.

* The feature can be changed according a type of model. 

* Work to the vinyl tape should up from below.  

NOTE

INSTALLATION TOOLS

INSTALLATION PARTS

Name

Quantity

Shape

Installation plate

1 EA

Cloth tape

Connector

1 EA

Type "A" screw

5 EA

Type "B" screw

2 EA

Type "C" screw

2 EA

Remote control

holder

1 EA

1 EA (5.0 kW)

2 EA (6.6 kW)

The feature can be changed according to type of model.

Type “B” screw

5.0 kW : 

ڸ

Ø9.52 (3/8) 

ơ

 Ø12.7 (1/2)

6.6 kW : 

ڸ

Ø9.52 (3/8) 

ơ

 Ø12.7 (1/2)

 

ڹ

Ø15.88 (5/8) 

ơ

 Ø12.7 (1/2)

Screws for fixing panels are attached to decoration panel.

When Indoor unit (5.0/6.6 kW) is connected to the Multi Outdoor unit, use the connector.

Figure

Figure

Name

Screw driver

Electric drill

Measuring tape, Knife

Hole core drill

Spanner

Torque wrench

Multi-meter

Hexagonal wrench

Ammeter

Gas-leak detector

Thermometer, 

Level

Flaring tool set

Name

Select the best Location 

- There should not be any heat or steam near

the unit.

- Select a place where there are no obstacles

around of the unit.

- Make sure that condensation drainage can

be conveniently routed away.

- Do not install near a doorway.

- Ensure that the interval between a wall and

the left (or right) of the unit is more than
100mm. The unit should be installed as high
as possible on the wall, allowing a minimum
of 200 mm from ceiling.

- Use a metal detector to locate studs to pre-

vent unnecessary damage to the wall.

* UV-C Model Only

* The feature can be changed according to

type of model.

Outdoor unit

- If an awning is built over the unit to prevent

direct sunlight or rain exposure, make sure
that heat radiation from the condenser is not
restricted.

- Ensure that the space around the back and

sides is more than 300 mm. The space in
front of the unit should be more than 700 mm
of space.

- Do not place animals and plants in the path of

the warm air.

- Take the weight of the air conditioner into 

account and select a place where noise and
vibration are minimum.

- Select a place where the warm air and noise

from the air conditioner do not disturb 
neighbors.

A

C

B

B

INSTALLATION

More than

300

More than

300

Sunr

oof

Fence or

obstacles

More than

700

More than

600

(Unit : mm)

The gap between the indoor unit and ceil-
ing is needed more than 200 mm for dis-
assemble the air filter.

NOTE

- Do not use nails and/or screws to attach

indoor units to sheetrock, drywall,
plasterboard, tile, plywood, or similar
material types without proper anchors.
Indoor units must be securely, and properly
mounted and anchored or damage and/or
injury may result from improper installation.

Anchor

Anchor

Screw

mm

mm

6 x 30

4 x 50

Type

A

B

C*

Wall mounted

200

100

1 800

(Unit : mm)

- The feature can be changed according to

type of model.

6

5

Содержание AM07BP.NSJ

Страница 1: ...he appliance shall be installed in accordance with national wiring regulations Compliance with national gas regulations shall be observed Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules If the supply cord is damaged it must be replaced by the man ufacturer or its service agents or similarly qualified person in order to avoid a hazard Appliance s...

Страница 2: ...or con sumer purposes not a precision refrigerant system There is risk of damage or loss of property Do not install the unit in potentially explosive atmospheres Refrigerant for R32 Only WARNING The appliance shall be stored in a well ventilated area where the room size corresponds to the room area as specified for operation The appliance shall be stored in a room without continuously operating op...

Страница 3: ... Spanner Torque wrench Multi meter Hexagonal wrench Ammeter Gas leak detector Thermometer Level Flaring tool set Name Select the best Location There should not be any heat or steam near the unit Select a place where there are no obstacles around of the unit Make sure that condensation drainage can be conveniently routed away Do not install near a doorway Ensure that the interval between a wall and...

Страница 4: ...rrs removal 1 Completely remove all burrs from the cut cross section of pipe tube 2 While removing burrs put the end of the copper tube pipe in a downward direction while removing burrs location is also changed in order to avoid dropping burrs into the tubing Putting nut on Remove flare nuts attached to indoor and outdoor unit then put them on pipe tube having completed burr removal not possible t...

Страница 5: ...es according to color codes referring to the wiring diagram NOTE The power cord connected to unit should be selected according to the following national wiring regulations The supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord code designation 60245 IEC 57 H05RN F CAUTION Outdoor unit 1 Remove the tubing cover from the unit by loose...

Страница 6: ...r 2 Connect a field supplied vinyl hose to the drain nipple A If the hose is too long and hangs down fix it carefully to prevent kinks The feature can be changed according to type of model Do not raise Water leakage Tip of drain hose dipped in water Water leakage Ditch Less than 50mm gap Accumulated drain water Air Waving Water leakage B A C 6 6 kW 2 5 3 5 5 0 kW Forming the Piping Form the piping...

Страница 7: ...3 Reattach the cover by pushing it back into position If you press and hold the On Off button for 3 5 seconds instead of 6 seconds the unit will switch to the test operation In the test operation the unit blows out strong air for cooling for 18 minutes and then returns to the factory default settings This is performed when the unit is relocated or the refrigerant circuit is serviced Pump Down mean...

Страница 8: ...lti model refer to Multi outdoor unit installation manual Capacity kW Pipe Size Standard Length m Max Length Ⓐ m Max Elevation Ⓑ m Additional Re frigerant g m GAS LIQUID mm inch mm inch 2 5 3 5 Ø9 52 3 8 Ø6 35 1 4 7 5 20 10 20 5 0 Ø12 7 1 2 Ø6 35 1 4 7 5 20 10 20 6 6 Ø15 88 5 8 Ø6 35 1 4 7 5 30 15 30 Capacity Mode Indoor temperature Outdoor temperature 2 5 3 5 kW Cooling 18 C 32 C 15 C 48 C Heatin...