* How to enter the installer mode

* How to set the code

- Air conditioners should not be installed in

areas where corrosive gases, such as acid
or alkaline gas, are produced.

- Do not install the product where it could be

exposed to sea wind (salty wind) directly. It
can result corrosion on the product.
Corrosion, particularly on the condenser
and evaporator fins, could cause product
malfunction or inefficient performance.

- If outdoor unit is installed close to the sea-

side, it should avoid direct exposure to the
sea wind. Otherwise it needs additional
anticorrosion treatment on the heat
exchanger.

Installation guide at the
seaside

Selecting the location
(Outdoor Unit)

If the outdoor unit is to be installed close to
the seaside, then direct exposure to the sea
wind should be avoided.

Install the outdoor unit on the opposite side of
the sea wind direction.

In case of installing the outdoor unit on the
sea side, setup a windbreak to prevent sea
wind.

- It should be strong enough like concrete to

prevent the sea wind from the sea.

- The height and width should be more than

150% of the outdoor unit.

- Keep more than 70 cm of space between

outdoor unit and the windbreak for easy air
flow.

Select a well-drained place.

Sea wind

Sea wind

- If you can’t meet above guide line in the

seaside installation, please contact LG
Electronics for the additional
anticorrosion treatment.

- Periodic ( more than once/year ) cleaning

of the dust or salt particles stuck on the
heat exchanger by using water

* Do not use seawater when you clean up

the heat exchanger.

Sea wind

Windbreak

CAUTION

!

Manual the decor, air filter Assembly & Disassembly

Disassemble the decor  

Turn off the power and unplug the power cord. 

2

Pull the decor at the bottom of the indoor unit.  

Assemble the decor 

1

Turn off the power and unplug the power cord. 

2

Insert 3 or 4 hooks of the decor into gap of
the indoor unit certainly.  

Disassemble the air filter 

1

Turn off the power and unplug the power cord. 

Hold the knob of the air filter, Lift it up slightly.

Remove the decor from the indoor unit.  

3

Hold the knob of the air filter, lift it up
slightly and remove it from the unit.  

Push the nooks to assemble the decor.  

Assemble the air filter 

1

Turn off the power and unplug the power cord. 

Insert the hooks of the air filter into the
front grille.  

3

Push down hooks to assemble the air filter.  

4

Check side of the front grille for the air filter
assembled correctly.  

lf the air filter is not assembled correctly, Dust

and other substance come into the indoor unit.

lf look at the indoor unit from higher than it,

can assemble the air filter easily.  

The air filter can be broken when it is

bended.  

NOTE

CAUTION

!

* How to set the code

* How to enter the installer mode

Outdoor unit

Indoor unit

Outdoor unit

Indoor unit

A

B

A

B

Capacity is based on standard length and maximum allowable length is on the basis of relia-
bility. Additional refrigerant must be charged after 12.5 m (2.5/3.5 kW Model) / 7.5 m (5.0/6.6
kW Model)

Operation ranges

The table below indicates the temperature ranges the air conditioner can be Operated within.

During the installation and binding of Multi model, refer to Multi outdoor unit installation manual.

Capacity

(kW)

Pipe Size

Standard

Length

(m)

Max.

Length 

(m)

Max.

Elevation

(m)

Additional Re-

frigerant (g/m)

GAS

LIQUID

mm

inch

mm

inch

2.5/3.5

Ø9.52

3/8

Ø6.35

1/4

7.5

20

10

20

5.0

Ø12.7

1/2

Ø6.35

1/4

7.5

20

10

20

6.6

Ø15.88

5/8

Ø6.35

1/4

7.5

30

15

30

Capacity

Mode

Indoor temperature

Outdoor temperature

2.5/3.5 kW

Cooling

18 °C ~ 32 °C

-15 °C ~ 48 °C

Heating

16 °C ~ 30 °C

-15 °C ~ 24 °C

5.0/6.6 kW

Cooling

18 °C ~ 32 °C

-15 °C ~ 48 °C

Heating

16 °C ~ 30 °C

-10 °C ~ 24 °C

Piping Length and Elevation

Single Split Model

Capacity

(kW)

Pipe Size

GAS

LIQUID

mm

inch

mm

inch

1.5/2.1/2.5/3.5/4.2

Ø9.52

3/8

Ø6.35

1/4

5.0/6.6

Ø12.7

1/2

Ø6.35

1/4

Multi Model

CAUTION

!

Precautions about installation in regions with extreme snowfall and cold temper-
atures

To ensure the outdoor unit operates properly, certain measures are required in locations where there
is a possibility of heavy snowfall or severe wind chill or cold :  

1

Prepare for severe winter wind chills and heavy snowfall, even in areas of the country where these
are unusual phenomena. 

2

Position the outdoor unit so that its airflow fans are not buried by direct, heavy snowfall. 
If snow piles up and blocks the airflow, the system may malfunction.

3

Remove any snow that has accumulated 100 mm or more on the top of the outdoor unit.

4

Place the outdoor unit on a raised platform at least 500 mm higher than the aver- age annual snow-
fall for the area. If the frame width is wider than the outdoor unit, snow may accumulate.

5

Install a snow protection hood.

6

To prevent snow and heavy rain from entering the outdoor unit, install the suction and dis- charge
ducts facing away from direct winds.

7

Additionally, the following conditions should be taken into consideration when the unit operates in
defrost mode: 
- If the outdoor unit is installed in a highly humid environment (near an ocean, lake, etc.), en- sure

that the site is well-ventilated and has a lot of natural light. (Example: Install on a rooftop.)

TIPS FOR SAVING ENERGY

Here are some tips that will help you minimize the power consumption when you use the air

conditioner. You can use your air conditioner more efficiently by referring to the instructions

below:

•  Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.

•  Block sunlight with blinds or curtains while you are operating the air conditioner.

•  Keep doors or windows closed tightly while you are operating the air conditioner.

•  Adjust the direction of the air flow vertically or horizontally to circulate indoor air.

•  Speed up the fan to cool or warm indoor air quickly, in a short period of time.

•  Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used

for many hours.

•  Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or

weaken the cooling / dehumidifying functions.

For your records

Staple your receipt to this page in case you need it to prove the date of purchase or for warranty 

purposes. Write the model number and the serial number here:

Model number :

Serial number :

You can find them on a label on the side of each unit.

Dealer’s name :

Date of purchase :

15

16

Содержание AM07BP.NSJ

Страница 1: ...he appliance shall be installed in accordance with national wiring regulations Compliance with national gas regulations shall be observed Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules If the supply cord is damaged it must be replaced by the man ufacturer or its service agents or similarly qualified person in order to avoid a hazard Appliance s...

Страница 2: ...or con sumer purposes not a precision refrigerant system There is risk of damage or loss of property Do not install the unit in potentially explosive atmospheres Refrigerant for R32 Only WARNING The appliance shall be stored in a well ventilated area where the room size corresponds to the room area as specified for operation The appliance shall be stored in a room without continuously operating op...

Страница 3: ... Spanner Torque wrench Multi meter Hexagonal wrench Ammeter Gas leak detector Thermometer Level Flaring tool set Name Select the best Location There should not be any heat or steam near the unit Select a place where there are no obstacles around of the unit Make sure that condensation drainage can be conveniently routed away Do not install near a doorway Ensure that the interval between a wall and...

Страница 4: ...rrs removal 1 Completely remove all burrs from the cut cross section of pipe tube 2 While removing burrs put the end of the copper tube pipe in a downward direction while removing burrs location is also changed in order to avoid dropping burrs into the tubing Putting nut on Remove flare nuts attached to indoor and outdoor unit then put them on pipe tube having completed burr removal not possible t...

Страница 5: ...es according to color codes referring to the wiring diagram NOTE The power cord connected to unit should be selected according to the following national wiring regulations The supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord code designation 60245 IEC 57 H05RN F CAUTION Outdoor unit 1 Remove the tubing cover from the unit by loose...

Страница 6: ...r 2 Connect a field supplied vinyl hose to the drain nipple A If the hose is too long and hangs down fix it carefully to prevent kinks The feature can be changed according to type of model Do not raise Water leakage Tip of drain hose dipped in water Water leakage Ditch Less than 50mm gap Accumulated drain water Air Waving Water leakage B A C 6 6 kW 2 5 3 5 5 0 kW Forming the Piping Form the piping...

Страница 7: ...3 Reattach the cover by pushing it back into position If you press and hold the On Off button for 3 5 seconds instead of 6 seconds the unit will switch to the test operation In the test operation the unit blows out strong air for cooling for 18 minutes and then returns to the factory default settings This is performed when the unit is relocated or the refrigerant circuit is serviced Pump Down mean...

Страница 8: ...lti model refer to Multi outdoor unit installation manual Capacity kW Pipe Size Standard Length m Max Length Ⓐ m Max Elevation Ⓑ m Additional Re frigerant g m GAS LIQUID mm inch mm inch 2 5 3 5 Ø9 52 3 8 Ø6 35 1 4 7 5 20 10 20 5 0 Ø12 7 1 2 Ø6 35 1 4 7 5 20 10 20 6 6 Ø15 88 5 8 Ø6 35 1 4 7 5 30 15 30 Capacity Mode Indoor temperature Outdoor temperature 2 5 3 5 kW Cooling 18 C 32 C 15 C 48 C Heatin...

Отзывы: