36
OPTIONAL OPERATION
ENGLISH
NOTE
!
1. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.
2. Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
3. Factory Set(External Static Pressure) each Model
* If it is zero static pressure, please set value below Maximum value.
Model
Factory set (E.S.P.)
mmAq(Pa)
Lower Limit (E.S.P)
mmAq(Pa)
Upper Limit (E.S.P)
mmAq(Pa)
ABNQ18GM1T0
8(78)
2(20)
8(78)
ABNQ24GM1T0
8(78)
2(20)
10(98)
ABNQ30GM1T0
8(78)
2.5(25)
10(98)
ABNQ36GM3T0
8(79)
2(20)
8(78)
ABNQ48LM3T0
6(59)
5(50)
12(118)
ABNQ54LM3T0
6(59)
4(39)
14(137)
Model
Maximum Value
ABNQ18GM1T0
106
ABNQ24GM1T0
115
ABNQ30GM1T0
115
ABNQ36GM3T0
72
ABNQ48LM3T0
90
ABNQ54LM3T0
98
Model
Factory set (E.S.P.)
mmAq(Pa)
Lower Limit (E.S.P.)
mmAq(Pa)
Upper Limit (E.S.P.)
mmAq(Pa)
ABNW18GM1T1
6(59)
2(20)
15(147)
ABNQ18GM1T1
2(20)
15(147)
ABNW24GM1T1
2(20)
15(147)
ABNQ24GM1T1
2(20)
15(147)
ABNW30GM1T1
2.5(25)
15(147)
ABNQ30GM1T1
2.5(25)
15(147)
ABNW36GM3T1
2.5(25)
15(147)
ABNQ36GM31T1
2.5(25)
15(147)
ABNW48GM3T1
4(39)
15(147)
ABNQ48GM3T1
4(39)
15(147)
ABNW54GM3T1
4(39)
15(147)
ABNQ54GM3T1
4(39)
15(147)
Model
Maximum value
ABNW18GM1T1
115
ABNQ18GM1T1
ABNW24GM1T1
ABNQ24GM1T1
ABNW30GM1T1
ABNQ30GM1T1
ABNW36GM3T1
98
ABNQ36GM31T1
ABNW48GM3T1
ABNQ48GM3T1
ABNW54GM3T1
ABNQ54GM3T1
Содержание ABNQ18GM1T0