OPTIONAL OPERATION
ENGLISH
33
Select the remote control master/slave
using button.
3
4
1
Move to the Master/slave selection in the
menu using button and then it displays
as below.
2
5
Press and hold button for more
than 3 seconds to enter the installer
settings mode.
- If pressing only once briefly, it will
enter the user settings mode.
Make sure to press and hold for more
than 3 seconds.
❈
Set value for static pressure
01 : V-H
02 : F-H
03 : V-L
04 : F-L
Code value for
static pressure
Set value
Press button to save the setting.
Press button to exit.
If no button is selected for about
25 seconds after setup, it exits the setup
mode automatically.
If the button is not selected before you
exit, the changes will not apply.
Installer Setting - Static Pressure Setting
This function is applied to only duct type. Setting this in other cases will cause malfunction.
<Static Pressure Setting Table>
Pressure selection
Function
Zone state
ESP standard value
01
V-H
Variable
High
02
F-H
Fixed
High
03
V-L
Variable
Low
04
F-L
Fixed
Low