30
OPTIONAL OPERATION
ENGLISH
Installer Setting - Thermistor
This is the function to select the temperature sensor to judge the room temperature.
Select the location of indoor temperature
sensor (Thermistor) using button.
❈
Set value for sensor location
01 : Remote control
02 : Indoor unit
03 : 2TH
3
Press button to save the setting.
4
5
Move to the Selection of Indoor Temperature
Sensor (Thermistor) in the menu using
button and then, it displays as below.
2
Press and hold button for more
than 3 seconds to enter the installer
settings mode.
- If pressing only once briefly, it will
enter the user settings mode.
Make sure to press and hold for more
than 3 seconds.
1
Press button to exit.
If no button is selected for about
25 seconds after setup, it exits the setup
mode automatically.
If the button is not selected before you
exit, the changes will not apply.
Code value for
Room temperature
sensor (Thermistor)
Set value
Temperature sensor selection
Function
01
Remote controller
Operation in remote controller temperature sensor
02
Indoor unit
Operation in indoor unit temperature sensor
03
2TH
Cooling
Operation of higher temperature by comparing indoor unit's
and wired remote controller's temperature. (There are
products that operate at a lower temperature.)
Heating
Operation of lower temperature by comparing indoor unit's
and wired remote controller's temperature.
<Thermistor Table>
* The function of 2TH has different operation characteristics according to the product.