OPTIONAL OPERATION
ENGLISH
29
Installer Setting - E.S.P.
This is the function that decides the strength of the wind for each wind level and because this
function is to make the installation easier.
- If you set ESP incorrectly, the air conditioner may malfunction.
- This setting must be carried out by a certificated-technician.
Once entered the ESP setting mode
using button, it displays as below.
2
Select the level of ESP Fan Speed using
button. There are 5 levels in the
fan speed, SLOW
→
LOW
→
MED
→
HIGH
→
POW.
❈
The ESP set value can be
programmed 0~225.
3
Move to the ESP value settings using
button.
The ESP value numbers will blink.
(It is set 000 by default.)
4
Set the ESP value using button.
(The ESP value can be set from 1 up to
255, and 1 is the smallest value and
255 is the largest value.)
5
Function code,
ESP code
ESP value
Press and hold button for more
than 3 seconds to enter the installer
settings mode.
- If pressing only once briefly, it will
enter the user settings mode.
Make sure to press and hold for more
than 3 seconds.
1
ESP
Code value
ESP value
ESP
Fan Speed level
ESP level : 01~05
ESP level Fan Speed
01
02
03
04
05
SLOW
LOW
MED
HIGH
POW.